Inspections for the day of: Wednesday, August 21, 2002.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02583 Electrical Rough-In8/20/20028/21/20028/21/2002 12:00:00 AMAPART
###-#### joe u/g and pool bond ok 8/21/2002 12:49:08 PM
ELE02-02100 Electrical Rough-In8/20/20028/21/20028/21/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 08/20/2002 at 14:32:47. Contact: ###-####. walls ok 8/21/2002 12:27:03 PM
ELE02-01491 Final8/20/20028/21/20028/21/2002 12:00:00 AMAFAIL
Phone #: ###-#### corrections not made and more created need to meet with Jim S or Mike K, about voiding owner permit and having him secure contractor too take over work owner does not have proper knowledge of electrical, 8/21/2002 6:25:03 PM
ELE02-02296 Final8/21/20028/21/20028/21/2002 12:00:00 AMPPASS
tom this ele permit is connected to this bld permit bld02-00568; Phone #: ###-#### ok 8/21/2002 2:19:14 PM
ELE02-02206 Final8/21/20028/21/20028/21/2002 12:00:00 AMPPASS
###-#### ok 8/21/2002 2:54:07 PM
ELE02-01614 Final8/21/20028/21/20028/21/2002 12:00:00 AMPNH
garage code 7832; Phone #: ###-#### no access code did not work electriacl contractor at job site could not get access either 8/21/2002 4:27:48 PM
ELE02-02288 Electrical Rough-In8/21/20028/21/20028/21/2002 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 08/21/2002 at 09:13:31. Contact: ###-####. walls ok 8/21/2002 4:55:35 PM
ELE02-02528 Rough-In Permanent Service8/21/20028/21/20028/21/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 08/21/2002 at 09:56:57. Contact: ###-####. stop work posted need approved set of plans stating addition is for duplex, wiring does not match plans at job site ,or building permit , note building permit states addition for exsiting single family residence called electrical contractor 8/21/2002 4:02:38 PM
ELE02-02582 Permanent Service8/21/20028/21/20028/21/2002 12:00:00 AMPFAIL
SHAWN ; Phone #: ###-#### cor. posted called 250.104 asure wter pipe is bonded bond hot and cold at both wter heaters, 250.8 no SMS for bond or grd p/s disconnect, 110.3(B) sue manufactures breakers only sub panel, 200.6and 7 blk wires used as neutrals white,as phase 310.16 is feeder to sub panel #6,or#4 protect at proper amps called 8/21/2002 6:20:06 PM
ELE02-00608 Permanent Service8/21/20028/21/20028/21/2002 12:00:00 AMPFAIL
Phone #: ###-#### cor. posted called all corrections not made and needs to bond nipples with #2 as 250.66 states stills needs to install locknuts to meet intent of 300.10,and 12 8/22/2002 12:05:51 PM