BLD03-02347
| Extend Permit 180 days | 8/20/2007 | 8/20/2007 | | P | |
|
|
|
BLD07-01658
| FIRE-Final Inspection | 8/21/2007 | 8/21/2007 | 8/23/2007 11:24:24 AM | P | CANC |
|
|
Reschedlued for 8/23 PM.
|
FIR07-00587
| INSP-Final Inspection | 8/20/2007 | 8/21/2007 | 8/21/2007 5:29:46 PM | P | FAIL |
|
|
The permit card, review notes, approved plan documents and inspection record paperwork are to be on site at all times for verification of code compliance at the time of field inspection per conditon of the permit.
|
FIR07-00660
| INSP-Alarm Testing | 8/17/2007 | 8/21/2007 | 8/21/2007 5:25:27 PM | P | FAIL |
|
|
System account information is not set up with the monitoring company, phone line troubles failed to report, need to complete NFPA record of inspection and testing prior to scheduling final field acceptance testing-see review notes item #2.
|
FIR07-00146
| FIR-Aging Inspection | 8/21/2007 | 8/21/2007 | 8/21/2007 3:58:30 PM | | DEFR |
|
|
Work in progress.
|
BLD07-00919
| FIRE-Final Inspection | 8/21/2007 | 8/21/2007 | 8/21/2007 3:57:53 PM | P | PASS |
|
|
Fire life safety finaled.
|
FIR07-00715
| INSP-Final Inspection | 8/21/2007 | 8/21/2007 | 8/21/2007 3:56:49 PM | P | PASS |
|
|
FA modification work passed inspection, permit finaled.
|
FIR07-00448
| INSP-Sprinkler Rough-in/Hydro | 8/20/2007 | 8/21/2007 | 8/21/2007 3:53:48 PM | P | PART |
|
|
AG hydrostatic test passed, verified resubmitted plans on site, overhead is NOT approved for cover at this time due to upright head obstructions by insulation at the deck, also missing cold cavity protection for piping above the riser room and reception area.
|
BLD07-01441
| FIRE-Final Inspection | 8/21/2007 | 8/21/2007 | 8/21/2007 3:13:06 PM | P | FAIL |
|
|
Need to provide weatherproof enclosure for the roof mounted duct detector and provide means for functionality testing.
|
BLD07-01067
| FIRE-Final Inspection | 8/21/2007 | 8/21/2007 | 8/21/2007 3:11:23 PM | P | FAIL |
|
|
Locking hardware at the door to the shared restroom is not allowed-see approved plan annotations, need to relocate exit sign or provide passage only hardware at this location, need to provide means for testing the duct detector.
|
FIR07-00603
| INSP-Final Inspection | 8/20/2007 | 8/21/2007 | 8/21/2007 12:52:46 PM | A | PASS |
|
|
Correction items are complete, fire sprinkler permit finaled.
|
BLD06-03408
| FIRE-Final Inspection | 8/20/2007 | 8/21/2007 | 8/21/2007 12:36:39 PM | A | PART |
|
|
Final pending correction of fire sprinkler coverage at the basement storage area due to a new wall which disrupts design density.
|
FIR07-00599
| INSP-Final Inspection | 8/21/2007 | 8/21/2007 | 8/21/2007 12:12:08 PM | P | PASS |
|
|
Required corrections have been completed, final inspection passed, fire alarm permit finaled.
|
BLD07-00917
| FIRE-Final Inspection | 8/20/2007 | 8/21/2007 | 8/21/2007 12:10:49 PM | A | FAIL |
|
|
Missing required exit signs as indicated on approved plan set for the second floor level, also need to install one EM light and repair one existing EM light as annotated, remainder of life safety is acceptable.
|
FIR07-00599
| INSP-Final Inspection | 8/20/2007 | 8/21/2007 | 8/21/2007 12:07:51 PM | A | FAIL |
|
|
One overspaced SD at the third floor corridor as previously noted has not been relocated, the remainder of c/n items are complete.
|
BLD07-01121
| FIRE-Final Inspection | 8/20/2007 | 8/21/2007 | 8/21/2007 10:20:59 AM | A | PASS |
|
|
Fire life safety is acceptable, one additonal PFE installed while on site at location as discussed.
|
FIR07-00624
| INSP-Final Inspection | 8/21/2007 | 8/21/2007 | 8/21/2007 10:19:26 AM | P | PASS |
|
|
Fire sprinkler permit for the TI modifications passed.
|