FIR07-00595
| INSP-Sprinkler Rough-in | 8/21/2007 | 8/21/2007 | 8/22/2007 1:07:02 PM | P | PASS |
|
|
The remaining portion of underground supply is ok to cover. Needs hydro tested and flushed.
|
FIR06-00011
| INSP-Alarm Testing | 8/20/2007 | 8/21/2007 | 8/21/2007 5:48:29 PM | P | DONE |
|
|
See mike timmermans notes for areas inspected.
|
FIR07-00561
| INSP-Sprinkler Rough-in/Hydro | 8/20/2007 | 8/21/2007 | 8/21/2007 5:47:32 PM | A | CANC |
|
|
No time to make a return trip today
|
FIR05-00536
| INSP-Sprinkler Rough-in | 8/21/2007 | 8/21/2007 | 8/21/2007 5:06:28 PM | P | PASS |
|
|
See the city approved drawings for the area on the 3rd floor that is ok to cover. Also the rough-in inspection for the penthouse is passed except for areas marked on the plans.
|
FIR07-00517
| INSP-Sprinkler Rough-in | 8/20/2007 | 8/21/2007 | 8/21/2007 5:03:47 PM | A | PASS |
|
|
First floor piping is ok to cover. This is the only area inspected. There were some minor changes and per the installer as-builts are being resubmitted to the city.
|
FIR07-00561
| INSP-Final Inspection | 8/20/2007 | 8/21/2007 | 8/21/2007 2:54:33 PM | P | CANC |
|
|
dan ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Inspection cancelled from web by: Stan Beus
|
BLD07-00376
| FIRE-Final Inspection | 8/21/2007 | 8/21/2007 | 8/21/2007 2:34:37 PM | P | PASS |
|
|
Final approved per Troy
|
FIR07-00539
| INSP-Alarm Testing | 8/20/2007 | 8/21/2007 | 8/21/2007 12:23:56 PM | A | FAIL |
|
|
Lower the pull station, provide manometer testing for the four units on the roof and the two west units below the deck, drill holes in the roof top duct detector housings and test these four duct smoke detectors.
|
BLD07-00836
| FIRE-Final Inspection | 8/21/2007 | 8/21/2007 | 8/21/2007 12:13:40 PM | A | PASS |
|
|
life safety passed
|
FIR07-00130
| INSP-Sprinkler Rough-in/Hydro | 8/20/2007 | 8/21/2007 | 8/21/2007 10:32:48 AM | A | PASS |
|
|
The attic system hydro test passed.
|
FIR07-00561
| INSP-Sprinkler Rough-in | 8/20/2007 | 8/21/2007 | 8/21/2007 10:29:51 AM | A | FAIL |
|
|
See the city approved plans for painted head, obstruction and hanging insulation problems
|
BLD07-01317
| FIRE-Final Inspection | 8/20/2007 | 8/21/2007 | 8/21/2007 9:55:03 AM | A | PART |
|
|
Life safety passed
|