Inspections for the day of: Tuesday, August 21, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00595 INSP-Sprinkler Rough-in8/21/20078/21/20078/22/2007 1:07:02 PMPPASS
The remaining portion of underground supply is ok to cover. Needs hydro tested and flushed.
FIR06-00011 INSP-Alarm Testing8/20/20078/21/20078/21/2007 5:48:29 PMPDONE
See mike timmermans notes for areas inspected.
FIR07-00561 INSP-Sprinkler Rough-in/Hydro8/20/20078/21/20078/21/2007 5:47:32 PMACANC
No time to make a return trip today
FIR05-00536 INSP-Sprinkler Rough-in8/21/20078/21/20078/21/2007 5:06:28 PMPPASS
See the city approved drawings for the area on the 3rd floor that is ok to cover. Also the rough-in inspection for the penthouse is passed except for areas marked on the plans.
FIR07-00517 INSP-Sprinkler Rough-in8/20/20078/21/20078/21/2007 5:03:47 PMAPASS
First floor piping is ok to cover. This is the only area inspected. There were some minor changes and per the installer as-builts are being resubmitted to the city.
FIR07-00561 INSP-Final Inspection8/20/20078/21/20078/21/2007 2:54:33 PMPCANC
dan ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Inspection cancelled from web by: Stan Beus
BLD07-00376 FIRE-Final Inspection8/21/20078/21/20078/21/2007 2:34:37 PMPPASS
Final approved per Troy
FIR07-00539 INSP-Alarm Testing8/20/20078/21/20078/21/2007 12:23:56 PMAFAIL
Lower the pull station, provide manometer testing for the four units on the roof and the two west units below the deck, drill holes in the roof top duct detector housings and test these four duct smoke detectors.
BLD07-00836 FIRE-Final Inspection8/21/20078/21/20078/21/2007 12:13:40 PMAPASS
life safety passed
FIR07-00130 INSP-Sprinkler Rough-in/Hydro8/20/20078/21/20078/21/2007 10:32:48 AMAPASS
The attic system hydro test passed.
FIR07-00561 INSP-Sprinkler Rough-in8/20/20078/21/20078/21/2007 10:29:51 AMAFAIL
See the city approved plans for painted head, obstruction and hanging insulation problems
BLD07-01317 FIRE-Final Inspection8/20/20078/21/20078/21/2007 9:55:03 AMAPART
Life safety passed