Inspections for the day of: Thursday, August 21, 2008.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01998 Final8/21/20088/21/20088/21/2008 3:48:01 PMPPASS
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA ok to final
ESC08-00141 General Inspection8/21/20088/21/20088/21/2008 3:14:06 PMPPART
looked ok
ESC08-00413 General Inspection8/21/20088/21/20088/21/2008 3:13:17 PMPPART
looked ok
ESC08-00237 General Inspection8/21/20088/21/20088/21/2008 3:12:02 PMPPART
looked ok
ESC07-01577 General Inspection8/21/20088/21/20088/21/2008 3:11:12 PMAPART
looked ok
ESC08-00363 General Inspection8/21/20088/21/20088/21/2008 3:10:02 PMAPART
looked ok
ELE08-02318 Final8/21/20088/21/20088/21/2008 3:07:08 PMPPASS
ok to final, no esc this project
ELE08-02317 Final8/21/20088/21/20088/21/2008 3:05:44 PMPPASS
ok to final, no esc this project
ELE08-02252 Final8/21/20088/21/20088/21/2008 3:04:42 PMPPASS
ok to final, no esc this project
ELE08-02218 Final8/21/20088/21/20088/21/2008 3:03:22 PMPPASS
ok to final, no esc this project
ELE08-02183 Final8/21/20088/21/20088/21/2008 3:01:59 PMPPASS
ok to final, no esc this project
ELE08-02023 Final8/21/20088/21/20088/21/2008 2:59:55 PMPPASS
ok to final, no esc this project
ELE08-02014 Final8/21/20088/21/20088/21/2008 2:58:44 PMPPASS
ok to final, no esc this project
ELE08-02338 Permanent Service8/21/20088/21/20088/21/2008 2:10:13 PMPPASS
Dan- late afternoon if possible Phone #: ###-#### p/s o/h rec ok, no esc this project
ELE08-01296 Electrical Rough-In8/21/20088/21/20088/21/2008 1:33:17 PMPPART
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL front and rear soffits ok to cover anop
ELE08-01952 Permanent Service8/20/20088/21/20088/21/2008 12:29:54 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack met contractor,, left correction notice, NEC 250.94 shall provide intersystem bonding termination, 250.92(B) shall use listed devices for bonding raceway at service, 110.3(B) listed equipment shall be installed in accordance with instructions in labelling- contactors must not have over 5kaic available
ELE08-02337 Permanent Service8/21/20088/21/20088/21/2008 10:33:32 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack p/s u/g n ok, no esc this project
ELE08-00769 Final8/20/20088/21/20088/21/2008 9:54:47 AMAPASS
Steve Phone #: ###-#### called contractor, ok to final, signed occupancy card
ELE08-01668 Final8/20/20088/21/20088/21/2008 9:07:44 AMAFAIL
Butch Phone #: ###-#### met contractor, left correction notice, BCC 4-05-33(A),(B) all equipment shall be listed by a nationally recognized testing laboratory
ELE08-02009 Electrical Rough-In8/20/20088/21/20088/21/2008 8:22:01 AMAPART
Phone #: ###-#### Internet Inspection Request from: Bryan McLaughlin store front floor and soffits anop ok to cover, no esc this project
ELE08-02009 Permanent Service8/21/20088/21/20088/21/2008 8:21:36 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bryan McLaughlin p/s, exst gear line-up, n, ok, 1 meter only, no esc this project