ELE08-01998
| Final | 8/21/2008 | 8/21/2008 | 8/21/2008 3:48:01 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA ok to final
|
ESC08-00141
| General Inspection | 8/21/2008 | 8/21/2008 | 8/21/2008 3:14:06 PM | P | PART |
|
|
looked ok
|
ESC08-00413
| General Inspection | 8/21/2008 | 8/21/2008 | 8/21/2008 3:13:17 PM | P | PART |
|
|
looked ok
|
ESC08-00237
| General Inspection | 8/21/2008 | 8/21/2008 | 8/21/2008 3:12:02 PM | P | PART |
|
|
looked ok
|
ESC07-01577
| General Inspection | 8/21/2008 | 8/21/2008 | 8/21/2008 3:11:12 PM | A | PART |
|
|
looked ok
|
ESC08-00363
| General Inspection | 8/21/2008 | 8/21/2008 | 8/21/2008 3:10:02 PM | A | PART |
|
|
looked ok
|
ELE08-02318
| Final | 8/21/2008 | 8/21/2008 | 8/21/2008 3:07:08 PM | P | PASS |
|
|
ok to final, no esc this project
|
ELE08-02317
| Final | 8/21/2008 | 8/21/2008 | 8/21/2008 3:05:44 PM | P | PASS |
|
|
ok to final, no esc this project
|
ELE08-02252
| Final | 8/21/2008 | 8/21/2008 | 8/21/2008 3:04:42 PM | P | PASS |
|
|
ok to final, no esc this project
|
ELE08-02218
| Final | 8/21/2008 | 8/21/2008 | 8/21/2008 3:03:22 PM | P | PASS |
|
|
ok to final, no esc this project
|
ELE08-02183
| Final | 8/21/2008 | 8/21/2008 | 8/21/2008 3:01:59 PM | P | PASS |
|
|
ok to final, no esc this project
|
ELE08-02023
| Final | 8/21/2008 | 8/21/2008 | 8/21/2008 2:59:55 PM | P | PASS |
|
|
ok to final, no esc this project
|
ELE08-02014
| Final | 8/21/2008 | 8/21/2008 | 8/21/2008 2:58:44 PM | P | PASS |
|
|
ok to final, no esc this project
|
ELE08-02338
| Permanent Service | 8/21/2008 | 8/21/2008 | 8/21/2008 2:10:13 PM | P | PASS |
|
|
Dan- late afternoon if possible Phone #: ###-#### p/s o/h rec ok, no esc this project
|
ELE08-01296
| Electrical Rough-In | 8/21/2008 | 8/21/2008 | 8/21/2008 1:33:17 PM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL front and rear soffits ok to cover anop
|
ELE08-01952
| Permanent Service | 8/20/2008 | 8/21/2008 | 8/21/2008 12:29:54 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack met contractor,, left correction notice, NEC 250.94 shall provide intersystem bonding termination, 250.92(B) shall use listed devices for bonding raceway at service, 110.3(B) listed equipment shall be installed in accordance with instructions in labelling- contactors must not have over 5kaic available
|
ELE08-02337
| Permanent Service | 8/21/2008 | 8/21/2008 | 8/21/2008 10:33:32 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack p/s u/g n ok, no esc this project
|
ELE08-00769
| Final | 8/20/2008 | 8/21/2008 | 8/21/2008 9:54:47 AM | A | PASS |
|
|
Steve Phone #: ###-#### called contractor, ok to final, signed occupancy card
|
ELE08-01668
| Final | 8/20/2008 | 8/21/2008 | 8/21/2008 9:07:44 AM | A | FAIL |
|
|
Butch Phone #: ###-#### met contractor, left correction notice, BCC 4-05-33(A),(B) all equipment shall be listed by a nationally recognized testing laboratory
|
ELE08-02009
| Electrical Rough-In | 8/20/2008 | 8/21/2008 | 8/21/2008 8:22:01 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Bryan McLaughlin store front floor and soffits anop ok to cover, no esc this project
|
ELE08-02009
| Permanent Service | 8/21/2008 | 8/21/2008 | 8/21/2008 8:21:36 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Bryan McLaughlin p/s, exst gear line-up, n, ok, 1 meter only, no esc this project
|