FIR08-00573
| INSP-Sprinkler Rough-in | 8/21/2008 | 8/21/2008 | 8/21/2008 3:59:36 PM | P | DONE |
|
|
This inspection was to verify that the devices had been removed. I found the existing fire alarm system clear of any troubles.
|
MIS07-00089
| FIR-Final | 8/21/2008 | 8/21/2008 | 8/21/2008 2:56:01 PM | P | PASS |
|
|
life safety passed.
|
BLD08-00984
| FIRE-Final Inspection | 8/21/2008 | 8/21/2008 | 8/21/2008 2:55:38 PM | P | PASS |
|
|
Life safety passed
|
FIR08-00397
| INSP-Final Inspection | 8/21/2008 | 8/21/2008 | 8/21/2008 2:54:48 PM | P | PASS |
|
|
Permit finaled
|
BLD07-01201
| FIRE-Final Inspection | 8/20/2008 | 8/21/2008 | 8/21/2008 1:16:05 PM | A | FAIL |
|
|
This inspection was for the tenant at 10480. The insulation has not been adequately secured to the deck and is blocking the upright sprinkler head coverage and is laying on the sprinkler piping.
|
FIR08-00413
| INSP-Final Inspection | 8/21/2008 | 8/21/2008 | 8/21/2008 1:06:18 PM | P | PASS |
|
|
permit finaled
|
BLD08-01357
| FIRE-Final Inspection | 8/20/2008 | 8/21/2008 | 8/21/2008 11:14:45 AM | A | FAIL |
|
|
Need the project related fire alarm permit passed and the emergency light added in the warehouse and in the drivers room. All ofther items will be ok.
|
FIR08-00528
| INSP-Final Inspection | 8/20/2008 | 8/21/2008 | 8/21/2008 11:13:43 AM | A | FAIL |
|
|
The sample tubes have been corrected but we could not test the duct smoke detector since the gas had not been piped to the hvac unit.
|
FIR08-00487
| INSP-Sprinkler Rough-in/Hydro | 8/20/2008 | 8/21/2008 | 8/21/2008 11:11:41 AM | A | PASS |
|
|
The underground hydro test passed. A 3psi loss was noted.
|
BLD07-03240
| FIRE-Final Inspection | 8/20/2008 | 8/21/2008 | 8/21/2008 10:36:46 AM | A | PASS |
|
|
LIfe safety passed.
|
FIR07-00605
| INSP-Final Inspection | 8/20/2008 | 8/21/2008 | 8/21/2008 10:29:57 AM | A | FAIL |
|
|
There were no city approved drawings on site. I did however go ahead and test the audio/visuals and found one that was not operating. It was replaced and tested prior to me leaving. The spacing and candella have not been checked nor any of the initiating devices.
|