Inspections for the day of: Tuesday, August 21, 2012.
Number of inspections: 7
Percentage of inspections complete: 86 %
Percentage of inspections not complete: 14 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00237 INSP-Alarm Testing8/15/20128/15/2012 P 
Please call 30 min prior to arrival Phone #: ###-#### >> Inspection requested via web by Jeff Walton
FIR12-00412 INSP-Sprinkler Rough-in8/21/20128/21/20128/21/2012 5:20:56 PMPPART
Overhead work at the mens and womens restroom, yard service, and west entry vestibule/soffit are okay to cover. Locations marked and dated on plans.
FIR12-00430 INSP-Sprinkler Rough-in8/21/20128/21/20128/21/2012 5:18:46 PMPPART
Overhead work approved for cover.
BLD12-00702 FIRE-Final Inspection8/21/20128/21/20128/21/2012 5:17:30 PMPPASS
Life safety inspection passed.
FIR12-00355 INSP-Final Inspection8/21/20128/21/20128/21/2012 2:53:41 PMPPASS
Scope of fire sprinkler work completed. Final walkthrough passed.
BLD12-01302 FIRE-Final Inspection8/20/20128/21/20128/21/2012 2:52:11 PMAFAIL
Project related fire alarm permit final pending corrections, noted one EM light in need of repair, revise door hardware at two locations.
FIR12-00354 INSP-Sprinkler Rough-in/Hydro8/20/20128/21/20128/21/2012 2:50:01 PMAPART
Overhead hydrostatic test per NFPA completed acceptable. Also verified head location revision at the NW stair landing1st floor.