ELE13-01291
| Electrical Rough-In | 8/17/2017 | 8/21/2017 | 8/22/2017 11:50:29 AM | A | FAIL |
|
|
Contact John for heat trace rough in and talk bonding at water feature on park site. Phone #: ###-#### Inspection requested via web by Tom Betty Discussed requirements for new water feature between Annex and HQ. If standing water and public has access to wade in water pool requirements of article 680 apply. Contact stated this body of water is to have public access for wading. All Code requirements for a pool apply. 680.11- Underground is wiring is not permitted under a pool unless this wiring is necessary to supply pool equipment. 680.26(A)- The equipotential bonding required by 680.26 shall be installed to reduce voltage gradients in the pool area including 3 existing perimenter walls. 680.27(C)(3)- Radiant heating cables are not permitted under or in pool deck.
|
ELE17-02724
| Conference | 8/21/2017 | 8/21/2017 | 8/21/2017 2:43:54 PM | P | DONE |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Discussed conduit system originally installed supported by ceiling grid. All conduits supported by grid if untouched will be allowed to remain, if new wiring is added or conduits need attention due to poor condition all shall be supported independant of grid system unless manufacturers instructions stated grid system is designed for support of conduits.
|
ELE17-02618
| Final | 8/21/2017 | 8/21/2017 | 8/21/2017 1:24:29 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Called to have address changed to 1423 W. Grove st where receptacle is actually installed. Final ok
|
ELE17-02618
| Electrical Rough-In | 8/21/2017 | 8/21/2017 | 8/21/2017 1:23:16 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok
|
ELE17-02557
| Rough-In Permanent Service | 8/18/2017 | 8/21/2017 | 8/21/2017 10:50:13 AM | A | FAIL |
|
|
Should be open. If you have any questions please call Clay ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan See rough in for cover. 110.24- Available fault current shall be posted prior to permanent service inspection.
|
ELE17-02557
| Electrical Rough-In | 8/21/2017 | 8/21/2017 | 8/21/2017 10:50:05 AM | P | PASS |
|
|
Should be open. If you have any questions please call Clay ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan Walls and hardlid rough in ok cover
|
ELE17-02689
| Electrical Rough-In | 8/18/2017 | 8/21/2017 | 8/21/2017 10:16:27 AM | A | PASS |
|
|
Bonding and underground cover Phone #: ###-#### Inspection requested via web by Kevin Koomler Bond ran from equipment location to pool perimeter that will inspect in future, no shell due to non-metellic pool shell and LED lighting and underground rough in ok cover
|
ELE16-01667
| Final | 8/18/2017 | 8/21/2017 | 8/21/2017 8:58:40 AM | A | PART |
|
|
unit 105,107 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty 107 bath GFI in op and kitchen not complete. 105 TCO ok
|