Inspections for the day of: Tuesday, August 21, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBill VanDegrift
TitlePLM-INSPECTOR
Phone #794-9372
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM18-02703 Water and/or Sewer8/20/20188/21/20188/21/2018 2:56:32 PMAFAIL
Jason Phone #: ###-####
1) the cleanout on the building sewer is installed backwards
2) remove 2" and 4" ABS fittings and replace with PVC at tie in. ( can't mix materials)
3) use approved glue
4) pressure test PVC and water piping.
5) use two clamps at each joint on the water service piping
6) sleeve water at sewer crossing, 10 feet on each side of crossing.
7) provide a tapped fitting on the pressure sewer at the sump to blow out sewer.
8) provide 3' of cover on pressure sewer and water lines.
PLM18-03500 Groundwork8/20/20188/21/20188/21/2018 11:36:50 AMPPASS
James Lewis is Journeyman on job ###-#### Phone #: ###-#### Inspection requested via web by Candice Martin
PLM18-03500 Water and/or Sewer8/20/20188/21/20188/21/2018 11:36:17 AMPPASS
ready for water line only inspection. James Lewis is journeyman on the job ###-####. Phone #: ###-#### Inspection requested via web by Candice Martin
PLM18-01818 Plumbing Rough-in8/20/20188/21/20188/21/2018 11:11:54 AMAPART
Eron Phone #: ###-#### water ok, waste is for the underfloor only.
PLM18-00497 Final8/21/20188/21/20188/21/2018 10:31:03 AMAFAIL
Phone #: ###-#### Inspection requested via web by Brian Johansen correction not made
PLM18-03463 Water and/or Sewer8/21/20188/21/20188/21/2018 10:21:07 AMAPASS
PLM18-03463 Final8/21/20188/21/20188/21/2018 10:20:51 AMPPASS
PLM18-03463 Water and/or Sewer8/21/20188/21/20188/21/2018 10:20:33 AMAPASS
PLM18-01998 Plumbing Rough-in8/20/20188/21/20188/21/2018 10:04:33 AMAPASS
Jacob Phone #: ###-####
sewer ok to corner of building, capped.
PLM18-03374 Groundwork8/20/20188/21/20188/21/2018 9:46:09 AMAPART
24 hour interceptor test AM to AM Phone #: ###-#### Inspection requested via web by Ben Taylor start 24 hour interceptor test
PLM18-03570 Water and/or Sewer8/20/20188/21/20188/21/2018 7:48:14 AMAPASS
Phone #: ###-#### Inspection requested via web by matt ford sw final ok
PLM18-03570 Final8/21/20188/21/20188/21/2018 7:47:51 AMPPASS
Phone #: ###-#### Inspection requested via web by matt ford