Inspections for the day of: Friday, August 22, 2003.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBill VanDegrift
TitlePLM-INSPECTOR
Phone #794-9372
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM03-02450 Final8/19/20038/22/20038/22/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 8/19/2003 at 3:38:30 PM. Contact: ###-####. final ok 8/22/2003 9:45:44 AM
PLM03-01755 Final8/21/20038/22/20038/22/2003 12:00:00 AMAPASS
craig; Phone #: ###-#### Internet Inspection Request from: Annette Moore called in the wrong number 8/22/2003 10:36:25 AM
PLM03-02607 Sprinkler (Final)8/21/20038/22/20038/22/2003 12:00:00 AMAPASS
###-#### chad final ok 8/22/2003 9:57:17 AM
PLM03-02435 Plumbing Rough-in8/21/20038/22/20038/22/2003 12:00:00 AMAPART
FRANK YOUNG; Phone #: ###-#### Internet Inspection Request from: Pam Masselli above floor ri restrooms ok 8/22/2003 10:52:04 AM
PLM03-02587 Sprinkler (Final)8/21/20038/22/20038/22/2003 12:00:00 AMAPASS
final ok with test ports plugged 8/22/2003 11:39:30 AM
PLM03-00538 Final8/21/20038/22/20038/22/2003 12:00:00 AMAPASS
sw, rd final ok 8/22/2003 11:44:34 AM
PLM03-00397 Final8/21/20038/22/20038/22/2003 12:00:00 AMAFAIL
install funnells at floor drains by ice makers, air gap water to ice makers, room 336 incomplete, expose building drain c.o., calk sink in room 122, r.p. required on chemical feed at washer, calk 3 comp sink, install grates on all floor sinks, calk d.f. turn down t&p drain , h.b.v.b. required on boiler drain in pool equipment room, test r.p. in pool equipment room, remove sheetrock screws on c.o. covers, calk toilets in public restrooms. 8/22/2003 5:02:52 PM
PLM03-02064 Final8/21/20038/22/20038/22/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 8/21/2003 at 5:15:57 PM. Contact: ###-####. final ok 8/22/2003 10:36:04 AM
PLM03-00687 Final8/22/20038/22/20038/22/2003 12:00:00 AMPPASS
underground -mike; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie final ok this is a final not an underground 8/22/2003 1:28:16 PM
PLM03-01653 Final8/22/20038/22/20038/22/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 8/22/2003 at 8:52:27 AM. Contact: ###-####. final ok 8/22/2003 3:39:40 PM
PLM03-01898 Final8/22/20038/22/20038/22/2003 12:00:00 AMPFAIL
house ok needs sprinkler permit 8/22/2003 1:47:44 PM