Inspections for the day of: Friday, August 22, 2003.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00359 INSP-Final Inspection8/20/20038/22/20038/22/2003 12:00:00 AMAFAIL
Sync strobes in room 181 (av5-17) and in corridor 152, horns in mech. room 218 are not 15db above ambient sound level, provide map for facp, provide locks on breakers, strobes in Press 100g and storage 189c exceed maximum coverage off wall (see plan). THIS WAS A PARTIAL INSPECTION. It appears plans and review notes have not been followed. I'm requesting the fire alarm contractor to reinspect before my next inspection 8/22/2003 1:59:49 PM
FIR03-00442 INSP-Final Inspection8/21/20038/22/20038/22/2003 12:00:00 AMAFAIL
rod; Phone #: ###-#### Could not due inspection since the gas was not turned on to the appliances under the hood 8/22/2003 9:20:04 AM
FIR03-00387 INSP-Supply line flush8/21/20038/22/20038/22/2003 12:00:00 AMAPASS
fire sprinkles finaled 8/22/2003 9:56:43 AM
FIR03-00400 INSP-Final Inspection8/21/20038/22/20038/22/2003 12:00:00 AMAPASS
MIKE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
FIR03-00374 INSP-Sprinkler Rough-in/Hydro8/21/20038/22/20038/22/2003 12:00:00 AMAPART
sam; Phone #: ###-#### Underground supply from riser in the north building to the end of the first length of pipe is ok to cover, approx 20' 8/22/2003 11:37:53 AM
BLD03-00798 FIRE-Final Inspection8/21/20038/22/20038/22/2003 12:00:00 AMAPART
Life safety was given a Temp until the fire dept. access curbing is painted and signed per review notes 4 and 5 and the fire alarm system is finaled 8/22/2003 11:02:58 AM
BLD03-01008 FIRE-Final Inspection8/22/20038/22/20038/22/2003 12:00:00 AMAPASS
fire life safety, fire alarm and fire sprinklers finaled
FIR03-00379 INSP-Final Inspection8/22/20038/22/20038/22/2003 12:00:00 AMAPART
The fire alarm system was given a temp occupancy with Sam Rogers permission until the system has been tested and finaled
FIR03-00228 INSP-Final Inspection8/22/20038/22/20038/22/2003 12:00:00 AMPPASS
Fire sprinklers finaled. Inspector program shows the resubmitted plans dated 8/11 have not been picked up yet, but the plans are here on site. I'm doc finaling it.
BLD02-02988 FIRE-Final Inspection8/22/20038/22/20038/22/2003 12:00:00 AMPPASS
Fire life safety, fire alarm and fire sprinklers finaled
FIR03-00399 INSP-Final Inspection8/22/20038/22/20038/22/2003 12:00:00 AMPPASS
FIR03-00209 INSP-Final Inspection8/22/20038/22/20038/22/2003 12:00:00 AMPPASS
BLD03-01253 FIRE-Final Inspection8/22/20038/22/20038/22/2003 12:00:00 AMPPASS
fire alarm system finaled. OK for perm occupancy
FIR03-00324 INSP-Final Inspection8/22/20038/22/20038/22/2003 12:00:00 AMPPASS
michelle; Phone #: ###-#### Internet Inspection Request from: Marc Lileks