Inspections for the day of: Monday, August 22, 2005.
Number of inspections: 13
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00266 INSP-Sprinkler Rough-in8/16/20058/17/2005 A 
###-#### - bruce Note: after morning 9:00 ish
MIS05-00056 FIR-Final8/19/20058/22/20058/23/2005 11:20:20 AMPPASS
Fire life safety is satisfactory.
BLD05-01718 FIRE-Final Inspection8/19/20058/22/20058/22/2005 4:34:32 PMPNR
Not ready for inspection, on site discussion with Jim regarding fire ext. locations, addressing, duct smoke remote annunciators, and door hardware.
BLD05-00287 FIRE-Final Inspection8/22/20058/22/20058/22/2005 4:02:45 PMPFAIL
The provided fire extinguishers must be mounted on the wall with handle no higher than 48", door sticker must meet current IFC code verbage as spelled out in review notes.
BLD04-02128 FIRE-Final Inspection8/22/20058/22/20058/22/2005 3:40:03 PMPPASS
Exit sign powered discharge light is manufacturer listed and UL approved per the provided paperwork. Life safety finaled.
FIR05-00473 INSP-Sprinkler Rough-in8/22/20058/22/20058/22/2005 3:03:06 PMPFAIL
Two arm overs in the lobby area have overspaced hangers, one pendent head in the lobby is overspaced from the adjacent wall.
FIR05-00308 INSP-Final Inspection8/22/20058/22/20058/22/2005 2:21:36 PMPPASS
Fire alarm permit finaled, strobe height is satisfactory.
FIR05-00262 INSP-Final Inspection8/22/20058/22/20058/22/2005 2:20:17 PMPPASS
Fire alarm permit is finaled.
FIR05-00186 INSP-Final Inspection8/19/20058/22/20058/22/2005 2:02:40 PMAPART
Testing today included Fred Meyer, Honks and Heart and Home stores. The outside bell at Fred Meyers failed to operate, a manual pull station at the main exit from the Heart and Home store is mounted too high, all other items in these areas tested today are acceptable.
FIR05-00446 INSP-Sprinkler Rough-in8/22/20058/22/20058/22/2005 1:46:16 PMPPART
Underground fire supply line is good for cover, per contractor the PIV has been relocated to avoid a sidewalk, this change to be reflected on as-built drawings.
BLD05-00353 FIRE-Final Inspection8/18/20058/22/20058/22/2005 10:25:43 AMAPASS
Life safety is satisfactory, the main entry door manual flush bolts have been removed.
BLD05-01600 FIRE-Final Inspection8/19/20058/22/20058/22/2005 10:16:40 AMAPART
Temporary occupancy approved with Sam Rogers permission pending completion of an FIR permit to add one fire sprinkler head due to ductwork obstruction. All other life safety issues are acceptable.
BLD03-02192 FIRE-Final Inspection8/19/20058/22/20058/22/2005 8:56:30 AMAPASS
Fire life safety passed inspection.