ELE06-01002
| ELE-Aging Inspection | 8/22/2006 | 8/22/2006 | 8/23/2006 3:05:03 PM | | DONE |
|
|
called, left message to call for inspection
|
ELE06-02790
| Electrical Rough-In | 8/22/2006 | 8/22/2006 | 8/22/2006 4:11:35 PM | P | PART |
|
|
gerald - Note: bounding grid; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles bond to grid ok only, u/g shall not have more than 360 bends, called contr to recall for u/g
|
ELE06-02928
| Rough-In Permanent Service | 8/22/2006 | 8/22/2006 | 8/22/2006 4:09:01 PM | P | FAIL |
|
|
Joe; Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt called contr, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 in walls of combustible material, boxes shall be flush with finished surface, 110.26(A) there shall be no foreign wiring in work space about panels, BCC address shall be posted, approved plans shall be on job, units and respective meters shall be identified, all make-up shall be done-fixtures installed
|
ELE06-03096
| Electrical Rough-In | 8/22/2006 | 8/22/2006 | 8/22/2006 3:08:16 PM | P | PART |
|
|
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g elect room area only, 1 90
|
ELE06-03054
| Final | 8/22/2006 | 8/22/2006 | 8/22/2006 2:14:48 PM | P | PASS |
|
|
chris - call 1/2hr prior for access (reinsp); Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
ELE06-03054
| Permanent Service | 8/22/2006 | 8/22/2006 | 8/22/2006 2:12:09 PM | P | PASS |
|
|
chris - call 1/2hr prior for access (reinsp); Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s o/h n ok
|
ELE06-03098
| Electrical Rough-In | 8/21/2006 | 8/22/2006 | 8/22/2006 10:29:03 AM | A | PART |
|
|
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover elect room area, 1-90
|
ELE06-01173
| Conference | 8/22/2006 | 8/22/2006 | 8/22/2006 10:10:22 AM | A | DONE |
|
|
contr called about listing, went to job, but listing sheets sent by supplier not sufficient to satisfy labelling requirements, told probably need field evaluation, told try to get resolution soon because of correction notice
|
ELE06-01341
| ELE-Aging Inspection | 8/22/2006 | 8/22/2006 | 8/22/2006 9:49:06 AM | | DONE |
|
|
drove by, suc
|
ELE06-02957
| Electrical Rough-In | 8/21/2006 | 8/22/2006 | 8/22/2006 9:34:46 AM | A | PART |
|
|
don - as late morning as possible (underground insp); Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g into elect room, incoming from east has 1 90, 1" to nw has 2 90s
|
ELE06-03088
| Rough-In Permanent Service | 8/18/2006 | 8/22/2006 | 8/22/2006 8:40:29 AM | A | PASS |
|
|
daryl; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ric ok, p/s u/g n ok
|
ELE06-00319
| Electrical Rough-In | 8/21/2006 | 8/22/2006 | 8/22/2006 8:14:25 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL ceilings ok to cover, up and down
|
ELE06-03096
| Electrical Rough-In | 8/21/2006 | 8/22/2006 | 8/22/2006 12:00:00 AM | A | CANC |
|
|
nr per ed//blb any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford
|