Inspections for the day of: Tuesday, August 22, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01002 ELE-Aging Inspection8/22/20068/22/20068/23/2006 3:05:03 PM DONE
called, left message to call for inspection
ELE06-02790 Electrical Rough-In8/22/20068/22/20068/22/2006 4:11:35 PMPPART
gerald - Note: bounding grid; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles bond to grid ok only, u/g shall not have more than 360 bends, called contr to recall for u/g
ELE06-02928 Rough-In Permanent Service8/22/20068/22/20068/22/2006 4:09:01 PMPFAIL
Joe; Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt called contr, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 in walls of combustible material, boxes shall be flush with finished surface, 110.26(A) there shall be no foreign wiring in work space about panels, BCC address shall be posted, approved plans shall be on job, units and respective meters shall be identified, all make-up shall be done-fixtures installed
ELE06-03096 Electrical Rough-In8/22/20068/22/20068/22/2006 3:08:16 PMPPART
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g elect room area only, 1 90
ELE06-03054 Final8/22/20068/22/20068/22/2006 2:14:48 PMPPASS
chris - call 1/2hr prior for access (reinsp); Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-03054 Permanent Service8/22/20068/22/20068/22/2006 2:12:09 PMPPASS
chris - call 1/2hr prior for access (reinsp); Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s o/h n ok
ELE06-03098 Electrical Rough-In8/21/20068/22/20068/22/2006 10:29:03 AMAPART
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover elect room area, 1-90
ELE06-01173 Conference8/22/20068/22/20068/22/2006 10:10:22 AMADONE
contr called about listing, went to job, but listing sheets sent by supplier not sufficient to satisfy labelling requirements, told probably need field evaluation, told try to get resolution soon because of correction notice
ELE06-01341 ELE-Aging Inspection8/22/20068/22/20068/22/2006 9:49:06 AM DONE
drove by, suc
ELE06-02957 Electrical Rough-In8/21/20068/22/20068/22/2006 9:34:46 AMAPART
don - as late morning as possible (underground insp); Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g into elect room, incoming from east has 1 90, 1" to nw has 2 90s
ELE06-03088 Rough-In Permanent Service8/18/20068/22/20068/22/2006 8:40:29 AMAPASS
daryl; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ric ok, p/s u/g n ok
ELE06-00319 Electrical Rough-In8/21/20068/22/20068/22/2006 8:14:25 AMAPASS
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL ceilings ok to cover, up and down
ELE06-03096 Electrical Rough-In8/21/20068/22/20068/22/2006 12:00:00 AMACANC
nr per ed//blb any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford