Inspections for the day of: Tuesday, August 22, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00559 INSP-Sprinkler Rough-in/Hydro8/22/20068/22/20068/22/2006 3:52:07 PMPPASS
Sprinkler piping is ok to cover
FIR06-00328 INSP-Sprinkler Rough-in/Hydro8/21/20068/22/20068/22/2006 2:48:38 PMPPASS
Sprinkler rough-in is passed. Piping in the office areas is ok to cover. Two esfr heads on the east side of the electrical room are overspaced. Earthquake bracing on the mains needs finished up. Above ground hydro test passed.
FIR06-00448 INSP-Sprinkler Rough-in8/22/20068/22/20068/22/2006 2:45:41 PMPPASS
All sprinkler piping in the open sales area is ok to cover. I spoke to an electrician about one exit sign theat was creating an obstruction to a pendnat head
MIS06-00132 FIR-Final8/21/20068/22/20068/22/2006 12:02:10 PMAFAIL
Indicator has not been installed at the main exit yet or the sticker.
FIR06-00446 INSP-Final Inspection8/21/20068/22/20068/22/2006 10:54:42 AMAFAIL
Can't give final until the ceiling tile has been installed. The ceiling transition from the hall to the open area needs a separation or upright protection will be required above the ceiling.
FIR05-00536 INSP-Sprinkler Rough-in/Hydro8/21/20068/22/20068/22/2006 9:00:54 AMAPASS
Sprinkler piping in the fire command center is ok to cover.
FIR05-00536 INSP-Supply line flush8/21/20068/22/20068/22/2006 8:29:16 AMAPASS
Underground flush passed.