Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02236 ELE-Aging Inspection8/22/20078/22/20078/23/2007 10:10:01 AM CANC
ELE07-01678 ELE-Aging Inspection8/22/20078/22/20078/23/2007 10:09:52 AM CANC
ELE07-00699 ELE-Aging Inspection8/22/20078/22/20078/23/2007 10:09:42 AM CANC
ELE07-00889 Final8/22/20078/22/20078/22/2007 4:30:54 PMPCANC
randy Phone #: ###-#### -please call 1/2 hr prior to inspection corr called 410.15(B)(3)(a) grd terminal shall be at hand hole, note addresses for house and tennant meters shall be correct
ELE07-02009 Final8/22/20078/22/20078/22/2007 4:26:12 PMPFAIL
randy Phone #: ###-#### - please call 1/2 hr prior to inspection called left message corr posted BCC &110.3(A) check all recepts for correct wiring found open neutral and loose neutral or grd, 110.3(B) provide max 20 amps for a/c (put fuses in wrong switch),
ELE07-02640 Rough-In Permanent Service8/22/20078/22/20078/22/2007 3:24:34 PMPPASS
steve Phone #: ###-#### p/s u/g for meters A&B ok
ELE07-02723 Final8/21/20078/22/20078/22/2007 3:01:40 PMPPASS
dan Phone #: ###-#### ok card signed
ELE07-02245 Final8/22/20078/22/20078/22/2007 2:35:51 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton needs 310 GRD PIGTAIL AT A/C DISCONNECT AND ALL RECEPTS UP HIGH NEEDS GFCI, CALLED final ok card signed
ELE07-02921 Temporary Service8/21/20078/22/20078/22/2007 1:12:17 PMPCANC
roger Phone #: ###-#### still needs clearence infront of main p/s remove all curbing in front of p/s
ELE07-02711 Final8/22/20078/22/20078/22/2007 12:29:57 PMPFAIL
dennis Phone #: ###-#### called corr. 110.3(B) manufactures breakers only, 210.8(B)(2) gfci for all recepts in commercial kit, 600.5 shall install required sign circuit as code states
ELE07-02852 Electrical Rough-In8/21/20078/22/20078/22/2007 10:56:28 AMAPASS
Scheduled by a contractor via Hello! on 8/21/2007 at 6:44:26 PM. Contact: ###-####. ok still needs outside boxes flush with siding
ELE07-01702 Final8/21/20078/22/20078/22/2007 10:36:13 AMAPASS
connie Phone #: ###-#### ok
ELE06-02704 Final8/21/20078/22/20078/22/2007 10:21:14 AMAPART
Please inspect for final on all floors of C-wing. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend ok
ELE06-03280 Final8/21/20078/22/20078/22/2007 10:20:52 AMAPART
Please inspect for final on all floors of D-wing. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend
ok
ELE06-03281 Final8/21/20078/22/20078/22/2007 10:20:29 AMAPART
Please inspect for final 3rd floor B-wing and all floors A-wing. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend ok
ELE07-02922 Final8/21/20078/22/20078/22/2007 12:00:00 AMPCANC
As early in the afternoon as possible, Idaho Power is going to turn off power @ 8am and will not reconnect until inspection is done. This is for a panel upgrade. Phone #: ###-#### Internet Inspection Request from: DJ Carman
ELE07-02922 Electrical Rough-In8/22/20078/22/20078/22/2007 12:00:00 AMPCANC