BLD03-02347
| Extend Permit 180 days | 8/20/2007 | 8/20/2007 | | P | |
|
|
|
FIR07-00091
| FIR-Aging Inspection | 8/22/2007 | 8/22/2007 | 8/23/2007 9:46:48 AM | | DEFR |
|
|
Work in progress.
|
FIR06-00759
| INSP-Final Inspection | 8/22/2007 | 8/22/2007 | 8/23/2007 9:46:01 AM | P | DEFR |
|
|
Rescheduled for 8/23
|
FIR07-00474
| INSP-Final Inspection | 8/22/2007 | 8/22/2007 | 8/23/2007 9:44:54 AM | P | DEFR |
|
|
Rescheduled for 8/23.
|
FIR07-00660
| INSP-Alarm Testing | 8/22/2007 | 8/22/2007 | 8/22/2007 3:27:25 PM | P | PASS |
|
|
Final fire alarm inspection passed.
|
FIR07-00587
| INSP-Final Inspection | 8/22/2007 | 8/22/2007 | 8/22/2007 3:25:35 PM | P | PASS |
|
|
Required corrections are complete, final fire sprinkler permit work inspection passed.
|
FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 8/21/2007 | 8/22/2007 | 8/22/2007 2:30:45 PM | A | PART |
|
|
OH hydrostatic test of the 4th floor west quad as marked on approved plan set passed, also inspected additonal corridor ceilings at the NW exit.
|
BLD07-01417
| FIRE-Final Inspection | 8/22/2007 | 8/22/2007 | 8/22/2007 1:35:36 PM | P | PASS |
|
|
Exit sign has been replaced per contractor, fire life safety finaled.
|
BLD07-01666
| FIRE-Final Inspection | 8/21/2007 | 8/22/2007 | 8/22/2007 1:31:43 PM | A | PASS |
|
|
Life safety inspection passed.
|
FIR07-00644
| INSP-Sprinkler Rough-in/Hydro | 8/22/2007 | 8/22/2007 | 8/22/2007 1:01:31 PM | P | FAIL |
|
|
Overspaced pendent head at one location.
|
FIR07-00645
| INSP-Final Inspection | 8/21/2007 | 8/22/2007 | 8/22/2007 12:58:01 PM | A | PART |
|
|
OH install is approved for cover at the drop ceilings, final pending tile and escutcheons.
|
FIR07-00265
| INSP-Final Inspection | 8/20/2007 | 8/22/2007 | 8/22/2007 11:57:41 AM | A | PASS |
|
|
Fire alarm modifications tested satisfactory, occupied L&D rooms verified per provided inspection and testing paperwork completed by the contractor.
|
BLD07-00917
| FIRE-Final Inspection | 8/21/2007 | 8/22/2007 | 8/22/2007 11:53:10 AM | A | PASS |
|
|
Required corrections have been completed, fire life safety passed inspection.
|
FIR07-00204
| INSP-Sprinkler Rough-in | 8/21/2007 | 8/22/2007 | 8/22/2007 10:37:02 AM | A | PART |
|
|
Overhead install at the drop ceilings for the core areas on the 3rd, 2nd and 1st floors are approved for cover.
|
BLD07-00808
| FIRE-Final Inspection | 8/21/2007 | 8/22/2007 | 8/22/2007 9:51:58 AM | A | FAIL |
|
|
Need project related fire alarm and sprinkler permits finaled prior to BLD life safety approval, noted door hardware at two exit locations is incorrect, discussed EM lighting, FA and FS permit issues.
|