Inspections for the day of: Friday, August 22, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-02305 Permanent Service8/21/20088/22/20088/22/2008 3:51:33 PMPPASS
service on sign in front of Collister Shopping Center Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA
p/s u/g new ok
ESC07-00608 General Inspection8/22/20088/22/20088/22/2008 3:20:35 PMPPART
site looks ok drain has filter on it
ELE08-00908 Electrical Rough-In8/22/20088/22/20088/22/2008 3:18:31 PMPPART
chris - ceiling grid Phone #: ###-####
no esc grid ceilings ok
ELE07-01778 Electrical Rough-In8/22/20088/22/20088/22/2008 2:58:10 PMPCANC
Peter Phone #: ###-#### see added p/s and conference
ELE07-01778 Conference8/22/20088/22/20088/22/2008 2:57:42 PMPDONE
Peter Phone #: ###-#### ok
ELE07-01778 Permanent Service8/22/20088/22/20088/22/2008 2:51:46 PMPPASS
Peter Phone #: ###-#### p/s u/g new ok
ELE08-02067 Electrical Rough-In8/22/20088/22/20088/22/2008 1:36:56 PMPPASS
ELE08-02067 Final8/22/20088/22/20088/22/2008 1:36:46 PMPPASS
ok
ELE08-01735 Final8/22/20088/22/20088/22/2008 12:32:49 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Celinda Winters corr. called
210.8(B) all 15&20 amp 125V recepts shall have gfci protection, 110.3(A) some kit recepts show open neutral, 314.3&110.3(B) shall provide bond bushings for all metallic fittings in non-metallic jbox, 314.43 shall not use screws inside of non-metallic jbox
ESC07-01007 General Inspection8/22/20088/22/20088/22/2008 12:23:55 PMPPART
looks ok
ELE05-01886 DOC - Permit Expired8/22/20088/22/20088/22/2008 9:33:33 AMAPASS
no action ever taken on permit
ESC08-00439 General Inspection8/22/20088/22/20088/22/2008 9:26:00 AMAPART
ok
ELE08-01787 Electrical Rough-In8/21/20088/22/20088/22/2008 9:24:57 AMAPART
kyle Phone #: ###-#### walls and hard ceilings pharmacy corr. posted for low voltage removed abandoned cables, and support cables
ELE08-02339 Temporary Service8/21/20088/22/20088/22/2008 8:19:19 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn no esc
t/s u/g new ok