FIR08-00491
| INSP-Sprinkler Rough-in | 8/21/2008 | 8/22/2008 | 8/22/2008 11:52:58 AM | P | PASS |
|
|
This inspection was for the underground supply cover. The two 45 elbows have been replaced with a single 90 elbow. The piping is approved for cover.
|
BLD07-01201
| FIRE-Final Inspection | 8/22/2008 | 8/22/2008 | 8/22/2008 11:49:51 AM | P | PART |
|
|
The insulation in tenant space 10480 is complete
|
BLD08-00472
| FIRE-Final Inspection | 8/22/2008 | 8/22/2008 | 8/22/2008 11:48:35 AM | P | FAIL |
|
|
Need the project related fire alarm permit to be finaled first.
|
BLD08-00154
| FIRE-Final Inspection | 8/22/2008 | 8/22/2008 | 8/22/2008 11:48:17 AM | P | FAIL |
|
|
Need the project related fire alarm permit to be finaled first.
|
FIR08-00363
| INSP-Final Inspection | 8/21/2008 | 8/22/2008 | 8/22/2008 11:30:37 AM | A | FAIL |
|
|
Provide an updated map, provide as-builts with corrected addresses, provide monitoring station printout, install the two remote annunciators as shown on the plans and remove the plastic tubes from the duct smoke detector
|
FIR08-00589
| INSP-Final Inspection | 8/21/2008 | 8/22/2008 | 8/22/2008 11:03:03 AM | P | CANC |
|
|
Internet Inspection Request from: Jeff Packham Inspection cancelled from web by: Jeff Packham
|
BLD08-01357
| FIRE-Final Inspection | 8/21/2008 | 8/22/2008 | 8/22/2008 10:23:52 AM | A | PASS |
|
|
Life safety passed
|
FIR08-00528
| INSP-Final Inspection | 8/22/2008 | 8/22/2008 | 8/22/2008 10:19:07 AM | P | PASS |
|
|
Permit finaled. I had the technician change the zone label from the tenant name to the tenant address.
|