Inspections for the day of: Friday, August 22, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00491 INSP-Sprinkler Rough-in8/21/20088/22/20088/22/2008 11:52:58 AMPPASS
This inspection was for the underground supply cover. The two 45 elbows have been replaced with a single 90 elbow. The piping is approved for cover.
BLD07-01201 FIRE-Final Inspection8/22/20088/22/20088/22/2008 11:49:51 AMPPART
The insulation in tenant space 10480 is complete
BLD08-00472 FIRE-Final Inspection8/22/20088/22/20088/22/2008 11:48:35 AMPFAIL
Need the project related fire alarm permit to be finaled first.
BLD08-00154 FIRE-Final Inspection8/22/20088/22/20088/22/2008 11:48:17 AMPFAIL
Need the project related fire alarm permit to be finaled first.
FIR08-00363 INSP-Final Inspection8/21/20088/22/20088/22/2008 11:30:37 AMAFAIL
Provide an updated map, provide as-builts with corrected addresses, provide monitoring station printout, install the two remote annunciators as shown on the plans and remove the plastic tubes from the duct smoke detector
FIR08-00589 INSP-Final Inspection8/21/20088/22/20088/22/2008 11:03:03 AMPCANC
Internet Inspection Request from: Jeff Packham Inspection cancelled from web by: Jeff Packham
BLD08-01357 FIRE-Final Inspection8/21/20088/22/20088/22/2008 10:23:52 AMAPASS
Life safety passed
FIR08-00528 INSP-Final Inspection8/22/20088/22/20088/22/2008 10:19:07 AMPPASS
Permit finaled. I had the technician change the zone label from the tenant name to the tenant address.