Inspections for the day of: Monday, August 22, 2011.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00305 Electrical Rough-In8/22/20118/22/20118/22/2011 2:49:10 PMPPASS
Contact: Roger Marose wall & ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden ok cover walls and ceiling re-pack room
ELE11-01822 Electrical Rough-In8/19/20118/22/20118/22/2011 1:58:41 PMPFAIL
Tom McGraw Phone #: ###-#### called, electrical contractor did not call for inspection, not ready, needs nail plates, free conductor length, ground metal boxes, outlet spacing, stapling
ELE11-01249 Electrical Rough-In8/22/20118/22/20118/22/2011 12:39:55 PMPPASS
Please call Ryker Phone #: ###-#### >> Inspection requested via web by Mark Sessions ok cover walls only 2 offices north east part remodel
ELE11-01676 Final8/19/20118/22/20118/22/2011 10:26:08 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by MARK PINNEY called electrician, left correction notice, NEC 330.30(B) shall strap mc cable within 12" of box, 112.12(A) shall close unused openings in boxes, 300.11 wiring shall not be supported by ceiling assembly- grid or tiles, did not check receptales, this was done as ceiling inspection only
ELE11-01828 Final8/19/20118/22/20118/22/2011 9:32:20 AMAPASS
Final to close out the permit thank you Brad Phone #: ###-#### >> Inspection requested via web by Brad Baker ok final, no card
ELE11-01887 Rough-In Permanent Service8/19/20118/22/20118/22/2011 8:58:17 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
ELE11-01562 Electrical Rough-In8/19/20118/22/20118/22/2011 8:04:39 AMAPASS
Early AM please--Underground concrete ground--Max Phone #: ###-#### ok to cover concrete concrete encased electrode, signed book