ELE11-00305
| Electrical Rough-In | 8/22/2011 | 8/22/2011 | 8/22/2011 2:49:10 PM | P | PASS |
|
|
Contact: Roger Marose wall & ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden ok cover walls and ceiling re-pack room
|
ELE11-01822
| Electrical Rough-In | 8/19/2011 | 8/22/2011 | 8/22/2011 1:58:41 PM | P | FAIL |
|
|
Tom McGraw Phone #: ###-#### called, electrical contractor did not call for inspection, not ready, needs nail plates, free conductor length, ground metal boxes, outlet spacing, stapling
|
ELE11-01249
| Electrical Rough-In | 8/22/2011 | 8/22/2011 | 8/22/2011 12:39:55 PM | P | PASS |
|
|
Please call Ryker Phone #: ###-#### >> Inspection requested via web by Mark Sessions ok cover walls only 2 offices north east part remodel
|
ELE11-01676
| Final | 8/19/2011 | 8/22/2011 | 8/22/2011 10:26:08 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by MARK PINNEY called electrician, left correction notice, NEC 330.30(B) shall strap mc cable within 12" of box, 112.12(A) shall close unused openings in boxes, 300.11 wiring shall not be supported by ceiling assembly- grid or tiles, did not check receptales, this was done as ceiling inspection only
|
ELE11-01828
| Final | 8/19/2011 | 8/22/2011 | 8/22/2011 9:32:20 AM | A | PASS |
|
|
Final to close out the permit thank you Brad Phone #: ###-#### >> Inspection requested via web by Brad Baker ok final, no card
|
ELE11-01887
| Rough-In Permanent Service | 8/19/2011 | 8/22/2011 | 8/22/2011 8:58:17 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
|
ELE11-01562
| Electrical Rough-In | 8/19/2011 | 8/22/2011 | 8/22/2011 8:04:39 AM | A | PASS |
|
|
Early AM please--Underground concrete ground--Max Phone #: ###-#### ok to cover concrete concrete encased electrode, signed book
|