BLD11-01966
| FIRE-Final Inspection | 8/22/2011 | 8/22/2011 | 8/22/2011 4:29:51 PM | P | CANC |
|
|
over booked
|
BLD11-01437
| FIRE-Conference | 8/22/2011 | 8/22/2011 | 8/22/2011 4:20:12 PM | P | PASS |
|
|
Discussed life safety requirements.
|
FIR11-00265
| INSP-Final Inspection | 8/19/2011 | 8/22/2011 | 8/22/2011 3:41:42 PM | P | PASS |
|
|
Permit finaled
|
FIR11-00325
| INSP-Final Inspection | 8/19/2011 | 8/22/2011 | 8/22/2011 3:37:26 PM | P | PASS |
|
|
Permit finaled
|
FIR11-00212
| INSP-Final Inspection | 8/19/2011 | 8/22/2011 | 8/22/2011 3:20:35 PM | P | PASS |
|
|
Permit finaled
|
FIR11-00139
| INSP-Final Inspection | 8/18/2011 | 8/22/2011 | 8/22/2011 3:19:58 PM | A | FAIL |
|
|
Todays inspection included the fire sprinkler interconnections. The tamper switches on the wet/dry risers and low air on the dry riser passed. The wet system flow switch and the dry system pressure switch did not ring the outside alarm bell. Also a walk through on all of the notification devices was performed. See the city approved plans for items needing corrected including the need for additional strobes.
|
FIR11-00415
| INSP-Sprinkler Rough-in | 8/19/2011 | 8/22/2011 | 8/22/2011 1:26:37 PM | A | PASS |
|
|
Rough-in passed sprinkler piping is ok to cover
|
FIR11-00334
| INSP-Sprinkler Rough-in | 8/19/2011 | 8/22/2011 | 8/22/2011 1:26:03 PM | A | PART |
|
|
The sprinkler piping is ok to cover except for the master bathroom. The pendant coverage in the master bathroom is blocked by a soffit over the bathtub.
|
FIR11-00334
| INSP-Supply line flush | 8/19/2011 | 8/22/2011 | 8/22/2011 1:24:27 PM | A | PASS |
|
|
Underground flush passed
|
BLD11-01865
| FIRE-Final Inspection | 8/19/2011 | 8/22/2011 | 8/22/2011 10:43:29 AM | A | PASS |
|
|
life safety passed.
|
BLD11-00610
| FIRE-Conference | 8/17/2011 | 8/22/2011 | | A | |
|
|
Troy-call Dixie for am meeting
|