ELE15-01348
| Conference | 8/22/2016 | 8/22/2016 | 8/23/2016 11:12:19 AM | P | DONE |
|
|
Inspect progress on panic hwd. in Garage EXP Discuss all Electrical Rooms in SWHQ , are we in compliance with 110.26 Personnel Doors? Phone #: ###-#### Inspection requested via web by Tom Betty Discussed if panic hardware require on all floors where electrical rooms are located. NEC 110.26(C)(3)- States equipment rated 800 amps or more that contain overcurrent devices, switching devices, or control devices, doors for egress located within 25' shall have panic hardware. As per Daryl DeGrange each room with a disconnecting means under 800 amp panic hardware is not required, if disconnects are rated 800 amp or larger panic hard ware required.
|
ELE16-01628
| Final | 8/19/2016 | 8/22/2016 | 8/22/2016 3:34:17 PM | P | NR |
|
|
Request for Temp occupancy . Call Ryan - ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton Outdoor egress not complete in front due to auning not in place yet. 210.8- All GFCI receptacles located in ceiling around bar shall be located in a readily accessible location.
|
ELE15-00495
| Rough-In Permanent Service | 8/22/2016 | 8/22/2016 | 8/22/2016 2:50:28 PM | P | CANC |
|
|
5 Story 4th floor Ballroom Ceiling for cover inspection. Contact is Mark Gibson ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves Needed rough in only.
|
ELE15-00495
| Electrical Rough-In | 8/22/2016 | 8/22/2016 | 8/22/2016 2:50:01 PM | P | PASS |
|
|
5 Story 4th floor Ballroom Ceiling for cover inspection. Contact is Mark Gibson ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves Ceiling inspection for this area for 2 3" conduits feeding roof top units. Rough in ok cover
|
ELE16-01652
| Electrical Rough-In | 8/21/2016 | 8/22/2016 | 8/22/2016 2:48:13 PM | P | PASS |
|
|
Underground north area of center core Phone #: ###-#### Inspection requested via web by John Rourke Discussed bonding around fountain area. Shall bond shell, 4 stubs for equipotential plane, metal spray housings. GFCI protection of LED lights depend on transformer type. North underground 20' to south rough in ok cover
|
ELE16-01421
| Final | 8/22/2016 | 8/22/2016 | 8/22/2016 1:16:41 PM | P | PASS |
|
|
Please call me half an hour before inspection for access. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Final ok
|
ELE16-02726
| Electrical Rough-In | 8/22/2016 | 8/22/2016 | 8/22/2016 12:28:41 PM | P | CANC |
|
|
Please call prior to inspection. ###-#### Phone #: ###-#### >> Inspection requested via web by BARRY KENDALL Inspection cancelled from web by: BARRY KENDALL
|
ELE16-02702
| Final | 8/18/2016 | 8/22/2016 | 8/22/2016 12:24:21 PM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by alfredo arteaga Needed permanent service inspection
|
ELE16-02702
| Permanent Service | 8/22/2016 | 8/22/2016 | 8/22/2016 12:23:34 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by alfredo arteaga 110.14- Aluminum conductors shal be coated with a oxide inhibitor when terminated. 250.53(A)(1)- Where rod is used as grounding electrode system it shall be supplemented by an additional rod.
|
ELE16-02681
| Electrical Rough-In | 8/22/2016 | 8/22/2016 | 8/22/2016 10:21:42 AM | A | PASS |
|
|
Phone #: 8694676 >> Inspection requested via mobile web by Barry Spencer Listing confirmed rough in ok
|
ELE16-02613
| Final | 8/19/2016 | 8/22/2016 | 8/22/2016 9:52:23 AM | A | NH |
|
|
Inspection requested via web by Randy Fletcher No answer at door no contact number provided.
|
ELE16-01991
| Final | 8/21/2016 | 8/22/2016 | 8/22/2016 9:33:49 AM | A | FAIL |
|
|
key on top of patio light Phone #: ###-#### Inspection requested via web by Therrin Robertson 230.70- Disconnect for detached garage shall disconnect power in the off position. 440.11- Furnace shall have a disconnecting means
|
ELE16-01990
| Final | 8/21/2016 | 8/22/2016 | 8/22/2016 9:30:14 AM | A | FAIL |
|
|
key on top of patio light Phone #: ###-#### Inspection requested via web by Therrin Robertson 230.70- Disconnect for detached garage shall disconnect power in the off position. 440.11- Furnace shall have a disconnecting means.
|
ELE16-02706
| Conference | 8/22/2016 | 8/22/2016 | 8/22/2016 8:59:18 AM | A | DONE |
|
|
Phone #: ###-#### Inspection requested via web by Ben Archibald Discussed the existing panel location in an existing bathroom. BCC 4-05-31(A)- Panel shall not be located in a bathroom. 310.15- Service feeders shall be sized properly for 200 amp panel from original install. Contractor to correct address should be 2100 . Broadway Ave.
|