Inspections for the day of: Tuesday, August 22, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00205 INSP-Sprinkler Rough-in/Hydro8/22/20178/22/20178/23/2017 12:29:33 PMPCANC
Needing an UG Hydro done. Please call Scott Powada 30mins before inspection Phone #: ###-#### Inspection requested via web by Kylee Wilson
FIR17-00412 INSP-Sprinkler Rough-in8/22/20178/22/20178/22/2017 3:01:19 PMPPASS
Underground rough to cover passed. Piping can be buried.
BLD17-01329 FIRE-Final Inspection8/22/20178/22/20178/22/2017 1:27:15 PMPCANC
Jeff Phone #: ###-####
NAF17-00054 INSP-Final8/21/20178/22/20178/22/2017 1:27:04 PMPFAIL
Provide a fire extinguisher as discussed for the second level.
FIR17-00277 INSP-Final Inspection8/21/20178/22/20178/22/2017 12:38:13 PMAFAIL
Notification needs to be modified in the new corridor system as discussed. No testing performed.
BLD13-02973 FIRE-Final Inspection8/21/20178/22/20178/22/2017 11:53:39 AMAFAIL
I only had time for a quick curtesy walk through today. Need the project related fire alarm and fire sprinkler permits finaled. Need ADA compliant hardware for all new doors, plans need to be re-submitted showing the three exteriro doors deleted with their associated exit signs and discharge lights, missing exit signs in Santuary, non-functional sings in Lobby and Santuary, need code compliant hood and suppression system for the type 1 hood in the Kitchen as noted on the approved drawings, missing electric alarm sprinkler bell, missing exit signs in the existing Classroom portion of building as shown on the plans. ....ect. No fire dept review notes on site.

Jessie Phone #: ###-####
FIR14-00205 INSP-Alarm Testing8/21/20178/22/20178/22/2017 11:47:34 AMAFAIL
I could not find a record of an undergrond hydro, missing two sprinkler canopies. in the east stairwell, need the pressure relief valve setup, need backflow certified, need head box signs and calc sticker, need three pendants removed where ceilings have not been installed. Leak is fixed.
FIR14-00701 INSP-Final Inspection8/18/20178/22/20178/22/2017 11:44:05 AMPFAIL
Need as-builts addressing the device locations and candella changes, hvac unit needs wired for shutdown, need map, need notification in short corridor, need flow switch tested.. All other devices tested
FIR17-00369 INSP-Final Inspection8/21/20178/22/20178/22/2017 8:18:39 AMAPASS
Rough-in passed. Piping can be covered.

John Phone #: ###-####
NAF17-00041 INSP-Sprinkler Rough-in/Hydro8/18/20178/22/20178/22/2017 7:00:42 AMAPASS
24 hour are test passed for the new addition
NAF16-00019 INSP-Final8/22/20178/22/20178/22/2017 12:00:00 AMAPASS
Rough in and flush and hydro were all complete there was never a final called in Phone #: ###-#### >> Inspection requested via web by Sam Ball