NAF18-00063
| INSP-Final | 8/22/2018 | 8/22/2018 | 8/22/2018 12:00:00 AM | P | FAIL |
|
|
Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
1-address needs posted
2-house keeping needs addressed
3-electrical panels need clearance
4- fire extinguishers need tages/location/clearances
|
NAF18-00065
| INSP-Final | 8/22/2018 | 8/22/2018 | 8/22/2018 12:00:00 AM | P | FAIL |
|
|
Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
1- fire ext need corrected. height/tag/location
2-cylindars need to be restrained
3-clearance for all electrical equipment shall be provided
4- address signage required for all buildings
|
NAF18-00092
| INSP-Final | 8/22/2018 | 8/22/2018 | 8/22/2018 12:00:00 AM | P | FAIL |
|
|
Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
-Not an inclusive or punch list
-Paint booth not included not part of this project will be permited at later date
1-remove all obstruciton from fire extinguishers
2-provide current tag on all fire extinguishers
3-provide address on all buildings
4-no storage over 12 fee in height
5-remove all hasp locks from exit doors
6-provide fire sprinkler protection in covered storage areas in rear of building
7-provide clear access to fire riser
8-provide clearance in front of electrical panels
9-provide clear path of egress from rear exit doors
10-provide small documents
discussed plaxtic curtain that is used on occasion for sanding and how it could impact fire sprinkler protection and interior finish materials
will need reinspect
|