MEC19-03715
| Final | 8/20/2019 | 8/22/2019 | 8/22/2019 3:59:45 PM | P | PASS |
|
|
INSTALLER DUSTIN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok
|
MEC19-03690
| Final | 8/21/2019 | 8/22/2019 | 8/22/2019 3:34:43 PM | P | PASS |
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- final ok
|
MEC19-02747
| Final | 8/21/2019 | 8/22/2019 | 8/22/2019 3:05:21 PM | P | FAIL |
|
|
will be home in the afternoon Phone #: ###-#### Inspection requested via web by Monica Lindsay- 1- need uv protection outside on lineset at a/c- 2- need to seal lineset thru foundation weather/rodent proof 3- need sediment trap on gas line between shut off valve and furnace 4- flue needs rerouted to maintain grade and omit horizontal off furnace 5- need to firecaulk penetrations on lineset by furnace into crawl
|
MEC19-03738
| Rough-in | 8/22/2019 | 8/22/2019 | 8/22/2019 2:36:37 PM | P | FAIL |
|
|
Robert-fireplace Phone #: ###-#### 1- need to remove blue painters tape and seal firestop in approved manner- 2- need to secure plastic behind flue almost touching in places 3- need framing completed and to dimensions in installation instructions
left do not cover sticker at fireplace
|
MEC19-03743
| Final | 8/21/2019 | 8/22/2019 | 8/22/2019 2:09:18 PM | P | PASS |
|
|
Please call Maddie on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- a/c coil ok
|
MEC19-03753
| Final | 8/21/2019 | 8/22/2019 | 8/22/2019 1:33:19 PM | P | PASS |
|
|
INSTALLER DAN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- RTU final ok
|
MEC19-03774
| Final | 8/22/2019 | 8/22/2019 | 8/22/2019 1:25:03 PM | P | CANC |
|
|
Please call Dave to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- scheduled for wrong day per phone with Kyle- will reschedule
|
MEC19-02805
| Final | 8/15/2019 | 8/22/2019 | 8/22/2019 1:01:56 PM | P | PASS |
|
|
Please have inspector call owner Christine at ###-#### when in route to home. Phone #: ###-#### Inspection requested via web by Carolyn Rudd- 2 furnaces 2 coilc 2 a/cs co ok
|
MEC19-03732
| Rough-in | 8/21/2019 | 8/22/2019 | 8/22/2019 11:49:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Sheldon Lebow- 2 fireplace R/Is ok- ok to cover
|
MEC19-03757
| Rough-in | 8/21/2019 | 8/22/2019 | 8/22/2019 11:48:56 AM | A | PASS |
|
|
ANY QUESTIONS CALL SAM ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- r/i ok range ducting- need to insulate outside air by final in garage- call in final when ready
|
MEC19-03757
| Pressure Test | 8/21/2019 | 8/22/2019 | 8/22/2019 11:47:58 AM | A | PASS |
|
|
ANY QUESTIONS CALL SAM ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- 20lb gas pass
|
MEC19-03621
| Rough-in | 8/21/2019 | 8/22/2019 | 8/22/2019 10:57:12 AM | A | PASS |
|
|
ANTHONY ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace R/I ok
|
MEC19-00762
| Final | 8/21/2019 | 8/22/2019 | 8/22/2019 10:40:06 AM | A | CANC |
|
|
garage code #4646 Phone #: ###-#### Inspection requested via web by Debbie Marino- final ok
|
MEC19-03144
| Final | 8/21/2019 | 8/22/2019 | 8/22/2019 10:23:43 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dennis Fox- will final out when homeowner pulls bath fan permit- rest is good- final ok
|
MEC19-03769
| Final | 8/22/2019 | 8/22/2019 | 8/22/2019 10:22:32 AM | P | PASS |
|
|
Ken Phone #: ###-####- these fans were looked at on other mech contractors permit- final ok
|
MEC19-03703
| Final | 8/19/2019 | 8/22/2019 | 8/22/2019 10:21:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Denise Colin- furnace a/c coil co ok
|
MEC19-03703
| Pressure Test | 8/19/2019 | 8/22/2019 | 8/22/2019 10:20:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Denise Colin- 5lb flue pass
|
MEC19-03569
| Rough-in | 8/21/2019 | 8/22/2019 | 8/22/2019 10:00:28 AM | A | PASS |
|
|
NATE ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace R/I ok
|
MEC19-03558
| Final | 8/21/2019 | 8/22/2019 | 8/22/2019 9:51:27 AM | A | PASS |
|
|
Please call Sarah ###-#### in route to inspection Phone #: ###-#### Inspection requested via web by Justin Osterhout- a/c coil co ok
|
MEC19-03586
| Final | 8/21/2019 | 8/22/2019 | 8/22/2019 9:34:02 AM | A | NH |
|
|
Please call Tim on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- called number listed no answer- went by know one home
|
MEC10-02322
| Mec-Aging Inspection | 8/22/2019 | 8/22/2019 | 8/22/2019 9:08:56 AM | | CANC |
|
|
permit reopened
|
MEC19-00107
| Mec-Aging Inspection | 8/22/2019 | 8/22/2019 | 8/22/2019 7:58:04 AM | | FAIL |
|
|
contractor needs to schedule inspection if works been done- permit will expire next aging if no activity
|
MEC19-03132
| Final | 8/21/2019 | 8/22/2019 | 8/21/2019 3:30:55 PM | A | PASS |
|
|
Bj 5730755 Inspection requested via web by william kerwin- final ok- card signed
|
MEC19-03132
| Final | 8/21/2019 | 8/22/2019 | 8/21/2019 1:31:36 PM | P | CANC |
|
|
Approed plans onsite bj 5730755 >> Inspection requested via web by william kerwin Inspection cancelled from web by: william kerwin
|