Inspections for the day of: Friday, August 23, 2002.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00265 INSP-Final Inspection8/26/20028/23/20028/26/2002 12:00:00 AMPPASS
BLD02-00505 FIRE-Final Inspection8/26/20028/23/20028/26/2002 12:00:00 AMPPART
okat to occupy the first floor of the new addition and exsisting school portion; second floor of new addition will require another inspection prior to occupancy
BLD02-01486 FIRE-Final Inspection8/23/20028/23/20028/23/2002 12:00:00 AMAFAIL
need access door for damper in corridor wall; fire alarm finaled
FIR02-00303 INSP-Final Inspection8/23/20028/23/20028/23/2002 12:00:00 AMAPASS
BLD02-00259 FIRE-Final Inspection8/23/20028/23/20028/23/2002 12:00:00 AMAPASS
FIR02-00223 INSP-Alarm Testing8/22/20028/23/20028/23/2002 12:00:00 AMAPASS
###-####
FIR02-00301 INSP-Alarm Testing8/22/20028/23/20028/23/2002 12:00:00 AMAPASS
###-####
FIR02-00274 INSP-Alarm Testing8/22/20028/23/20028/23/2002 12:00:00 AMAPASS
###-####
FIR02-00309 INSP-Sprinkler Rough-in/Hydro8/22/20028/23/20028/23/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 08/22/2002 at 16:07:34. Contact: ###-####. hydro on all overhead okay; tested wet system alarms okay; need to test dry system alarms/tampers; dry uprights not installed 8/26/2002 8:37:42 AM
BLD02-01372 FIRE-Conference8/22/20028/23/20028/23/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 08/22/2002 at 16:21:11. Contact: . temp okay per Dave Miller and completion of the fire alarm panel replacement 8/23/2002 8:26:57 AM
BLD02-01613 FIRE-Final Inspection8/23/20028/23/20028/23/2002 12:00:00 AMPPASS
jack; Phone #: ###-####
FIR02-00303 INSP-Alarm Testing8/23/20028/23/20028/23/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 08/23/2002 at 07:55:52. Contact: ###-####.
FIR02-00317 INSP-Alarm Testing8/23/20028/23/20028/23/2002 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 08/23/2002 at 08:00:25. Contact: ###-####. tested alarms; need to test the dry system alarms/tampers as it is now wet; detector at damper in 1 hour wall for damper release not working - damper will be kept closed until it can be repaired; elevator recall/shunt not tested as the elevator is not certified by state; alarms in new addition tested okay 8/26/2002 8:36:46 AM
BLD00-02062 FIRE-Final Inspection8/22/20028/23/20028/23/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 08/22/2002 at 13:44:11. Contact: ###-####. need address; move knox box to Americana side of building; zones defined for fire monitoring company; map at FACP and in knox box 8/23/2002 3:10:58 PM
FIR02-00309 INSP-Sprinkler Rough-in/Hydro8/22/20028/23/20028/23/2002 12:00:00 AMPPART
air test 24 hour air test okay on dry system 8/23/2002 1:28:18 PM
FIR01-00527 INSP-Final Inspection8/23/20028/23/20028/23/2002 12:00:00 AMPPASS
FIR02-00034 INSP-Final Inspection8/23/20028/23/20028/23/2002 12:00:00 AMPPASS
FIR02-00037 INSP-Final Inspection8/23/20028/23/20028/23/2002 12:00:00 AMPFAIL
need zones defined for monitoring company; map for knox box and FACP; address on building