Inspector Activity
Inspections for the day of:
Friday, August 23, 2002
.
Number of inspections:
18
Percentage of inspections complete:
100 %
Percentage of inspections not complete:
0 %
Contact Information
Inspector
Rick Jackson
Title
FIRE INSPECTOR
Phone #
794-1981
Permit Number
Description
Received
Requested
Completed
AM/PM
Disposition
FIR02-00265
INSP-Final Inspection
8/26/2002
8/23/2002
8/26/2002 12:00:00 AM
P
PASS
BLD02-00505
FIRE-Final Inspection
8/26/2002
8/23/2002
8/26/2002 12:00:00 AM
P
PART
okat to occupy the first floor of the new addition and exsisting school portion; second floor of new addition will require another inspection prior to occupancy
BLD02-01486
FIRE-Final Inspection
8/23/2002
8/23/2002
8/23/2002 12:00:00 AM
A
FAIL
need access door for damper in corridor wall; fire alarm finaled
FIR02-00303
INSP-Final Inspection
8/23/2002
8/23/2002
8/23/2002 12:00:00 AM
A
PASS
BLD02-00259
FIRE-Final Inspection
8/23/2002
8/23/2002
8/23/2002 12:00:00 AM
A
PASS
FIR02-00223
INSP-Alarm Testing
8/22/2002
8/23/2002
8/23/2002 12:00:00 AM
A
PASS
###-####
FIR02-00301
INSP-Alarm Testing
8/22/2002
8/23/2002
8/23/2002 12:00:00 AM
A
PASS
###-####
FIR02-00274
INSP-Alarm Testing
8/22/2002
8/23/2002
8/23/2002 12:00:00 AM
A
PASS
###-####
FIR02-00309
INSP-Sprinkler Rough-in/Hydro
8/22/2002
8/23/2002
8/23/2002 12:00:00 AM
A
PART
Scheduled by a contractor via Hello! on 08/22/2002 at 16:07:34. Contact: ###-####. hydro on all overhead okay; tested wet system alarms okay; need to test dry system alarms/tampers; dry uprights not installed 8/26/2002 8:37:42 AM
BLD02-01372
FIRE-Conference
8/22/2002
8/23/2002
8/23/2002 12:00:00 AM
A
PART
Scheduled by a contractor via Hello! on 08/22/2002 at 16:21:11. Contact:
. temp okay per Dave Miller and completion of the fire alarm panel replacement 8/23/2002 8:26:57 AM
BLD02-01613
FIRE-Final Inspection
8/23/2002
8/23/2002
8/23/2002 12:00:00 AM
P
PASS
jack; Phone #: ###-####
FIR02-00303
INSP-Alarm Testing
8/23/2002
8/23/2002
8/23/2002 12:00:00 AM
P
PASS
Scheduled by a contractor via Hello! on 08/23/2002 at 07:55:52. Contact: ###-####.
FIR02-00317
INSP-Alarm Testing
8/23/2002
8/23/2002
8/23/2002 12:00:00 AM
P
PART
Scheduled by a contractor via Hello! on 08/23/2002 at 08:00:25. Contact: ###-####. tested alarms; need to test the dry system alarms/tampers as it is now wet; detector at damper in 1 hour wall for damper release not working - damper will be kept closed until it can be repaired; elevator recall/shunt not tested as the elevator is not certified by state; alarms in new addition tested okay 8/26/2002 8:36:46 AM
BLD00-02062
FIRE-Final Inspection
8/22/2002
8/23/2002
8/23/2002 12:00:00 AM
P
FAIL
Scheduled by a contractor via Hello! on 08/22/2002 at 13:44:11. Contact: ###-####. need address; move knox box to Americana side of building; zones defined for fire monitoring company; map at FACP and in knox box 8/23/2002 3:10:58 PM
FIR02-00309
INSP-Sprinkler Rough-in/Hydro
8/22/2002
8/23/2002
8/23/2002 12:00:00 AM
P
PART
air test 24 hour air test okay on dry system 8/23/2002 1:28:18 PM
FIR01-00527
INSP-Final Inspection
8/23/2002
8/23/2002
8/23/2002 12:00:00 AM
P
PASS
FIR02-00034
INSP-Final Inspection
8/23/2002
8/23/2002
8/23/2002 12:00:00 AM
P
PASS
FIR02-00037
INSP-Final Inspection
8/23/2002
8/23/2002
8/23/2002 12:00:00 AM
P
FAIL
need zones defined for monitoring company; map for knox box and FACP; address on building