Inspections for the day of: Friday, August 23, 2002.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00088 INSP-Final Inspection8/20/20028/23/20028/23/2002 12:00:00 AMAPASS
fire alarm system finaled 8/26/2002 9:20:33 AM
BLD02-01675 FIRE-Final Inspection8/22/20028/23/20028/23/2002 12:00:00 AMAPASS
FIR02-00324 INSP-Final Inspection8/23/20028/23/20028/23/2002 12:00:00 AMAPART
provide in-duct detector for smoke damper in band practice, delete or relocate smoke detector in band practice, test makeup air units, provide adequate visual coverage in center courtyard, Provide approved fire alarm plans wih all required modifications by October 1, 2002 per Steve Minnis with the Boise Fire Dept.. A temporary occupancy was given per Steve Minnis permission