Inspections for the day of: Monday, August 23, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00236 INSP-Sprinkler Rough-in8/19/20048/23/20048/23/2004 12:00:00 AMACANC
Contact: Nate; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
FIR04-00236 INSP-Sprinkler Rough-in/Hydro8/20/20048/23/20048/23/2004 12:00:00 AMAPART
Provide sprinklers or insulation in the west overbuild side pockets. Provide missing earthquake bracing and sprig-up as marked on plans. Provide verification that sidesammys will work in 2 x 4's. 8/23/2004 2:09:15 PM
FIR04-00434 INSP-Sprinkler Rough-in/Hydro8/20/20048/23/20048/23/2004 12:00:00 AMPFAIL
Wrong sprinkler heads have been installed. Change out heads or resubmit. Hydro test and rough-in OK. Need alarms 8/23/2004 3:00:02 PM
BLD04-01672 FIRE-Final Inspection8/23/20048/23/20048/23/2004 12:00:00 AMPFAIL
Sprinkler pendants in backroom are overspaced and spaced too close in one spot. Sprinkler work will require permits. Provide approved door hardware on all doors per review note #22. Must unlock in a single motion. Remove deadbolt on the rear door. Building floor plans do not match what is installed. Resubmit plans, 2 copies, to city of boise. Reviewer is Dan Stuart, ###-####. Remove plastic exit signs. Provide verification HVAC unit has duct smoke detector per fire review note #35 and test 8/23/2004 4:19:12 PM
BLD04-01104 FIRE-Final Inspection8/23/20048/23/20048/23/2004 12:00:00 AMPCANC
Contractor has not fixed strobe problem yet 8/23/2004 2:57:02 PM