FIR05-00266
| INSP-Sprinkler Rough-in | 8/16/2005 | 8/17/2005 | | A | |
|
|
###-#### - bruce Note: after morning 9:00 ish
|
BLD04-02767
| FIRE-Final Inspection | 8/22/2005 | 8/23/2005 | 8/23/2005 4:07:39 PM | P | PART |
|
|
Temporary occupancy approved for the remodel/addition area with Sam Rogers permission pending the completion of the fire alarm and fire sprinkler work in the existing portions of the building. Life safety issues are acceptable for a temp. approval in the expanded sales area.
|
FIR05-00259
| INSP-Sprinkler Rough-in/Hydro | 8/23/2005 | 8/23/2005 | 8/23/2005 2:47:49 PM | P | PART |
|
|
Begin 24 hour air test of the dry system at 1:55 p.m 8/23/05 at 42psi.
|
FIR05-00217
| INSP-Final Inspection | 8/23/2005 | 8/23/2005 | 8/23/2005 2:40:14 PM | P | PASS |
|
|
Calculations for spacing have been verified. Fire sprinkler permit finaled.
|
FIR05-00186
| INSP-Final Inspection | 8/22/2005 | 8/23/2005 | 8/23/2005 2:33:59 PM | A | FAIL |
|
|
One horn strobe device in the Stage Coach theater seating area failed to operate, an additional horn strobe is required in the lounge area at Mikes Restaurant due to a mirrored soffit obstruction, one storage room adjacent to the lounge is missing notification, several pull stations are mounted 1/2" too high, todays inspection completes all areas up to the first west fire separation wall.
|
BLD04-01866
| FIRE-Final Inspection | 8/22/2005 | 8/23/2005 | 8/23/2005 10:19:58 AM | A | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00448
| INSP-Final Inspection | 8/22/2005 | 8/23/2005 | 8/23/2005 10:17:25 AM | A | FAIL |
|
|
Pendent head in womens restroom is blocked by a surface mounted light fixture, one head in the sales floor area is blocked by its proximity to a steel column, the remaining rough-in issues are acceptable.
|
BLD03-03031
| FIRE-Final Inspection | 8/23/2005 | 8/23/2005 | 8/23/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled.
|