Inspections for the day of: Wednesday, August 23, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01902 ELE-Aging Inspection8/23/20068/23/20068/25/2006 7:49:30 AM CANC
ELE04-01830 Electrical Rough-In8/22/20068/23/20068/23/2006 3:24:42 PMPPASS
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
storage basement ok
ELE06-01275 Rough-In Permanent Service8/23/20068/23/20068/23/2006 2:50:50 PMPPART
This will be the rough in for the x-ray room and a few walls. Please talk with Marvin Miller on site. Thank you; Phone #: ###-#### Internet Inspection Request
from: Laura Longshaw
walls business and dr offices, xray rm and hard ceiling parking garage
ELE06-00460 Electrical Rough-In8/23/20068/23/20068/23/2006 2:11:47 PMPNR
Duke; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
needs p/s not r/i, also needs to label house meter
ELE06-02992 Electrical Rough-In8/23/20068/23/20068/23/2006 1:28:10 PMPPART
###-#### ken ok for insulation only, corr. met owner's father, needs grd pigtails for switches, and 6" free length of conductor for all equip grds, told them that at time of conference
ELE06-03104 Temporary Service8/23/20068/23/20068/23/2006 12:59:12 PMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
t/s u/g new ok
ELE06-02443 Final8/23/20068/23/20068/23/2006 12:26:12 PMPPASS
gary; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
ELE06-03137 Rough-In Permanent Service8/23/20068/23/20068/23/2006 10:31:52 AMAPART
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson no p/s corr. needs 1/0 cu. 3/0 alum. to bond water 250.66, 250.64(C) shall not splice GEC,
r/i ok survey for nail plates called
ELE06-02515 Final8/22/20068/23/20068/23/2006 9:43:23 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok no
card
ELE06-00165 Final8/22/20068/23/20068/23/2006 9:42:50 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok called needs labels for both p/s, bond H&C water no card
ELE06-03090 Final8/21/20068/23/20068/23/2006 9:14:19 AMAFAIL
jessica - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 230.28 needs stiff let to oppose strain not guy kit, 110.3(B) use manufactures breakers only, 250.64(B) protect #8 GEC or install #6, 250.52(A)(1)or104(A)(1) grd or bond water system corr. called
ELE06-01236 Final8/21/20068/23/20068/23/2006 8:17:36 AMAFAIL
if locked the key is on top of the furnace behind the vent; Phone #: ###-#### Internet Inspection Request from: steve creswell corr. called left message, 410.8 clearence MB closet fixture, 408.4 panel directory