ELE06-01902
| ELE-Aging Inspection | 8/23/2006 | 8/23/2006 | 8/25/2006 7:49:30 AM | | CANC |
|
|
|
ELE04-01830
| Electrical Rough-In | 8/22/2006 | 8/23/2006 | 8/23/2006 3:24:42 PM | P | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley storage basement ok
|
ELE06-01275
| Rough-In Permanent Service | 8/23/2006 | 8/23/2006 | 8/23/2006 2:50:50 PM | P | PART |
|
|
This will be the rough in for the x-ray room and a few walls. Please talk with Marvin Miller on site. Thank you; Phone #: ###-#### Internet Inspection Request from: Laura Longshaw walls business and dr offices, xray rm and hard ceiling parking garage
|
ELE06-00460
| Electrical Rough-In | 8/23/2006 | 8/23/2006 | 8/23/2006 2:11:47 PM | P | NR |
|
|
Duke; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt needs p/s not r/i, also needs to label house meter
|
ELE06-02992
| Electrical Rough-In | 8/23/2006 | 8/23/2006 | 8/23/2006 1:28:10 PM | P | PART |
|
|
###-#### ken ok for insulation only, corr. met owner's father, needs grd pigtails for switches, and 6" free length of conductor for all equip grds, told them that at time of conference
|
ELE06-03104
| Temporary Service | 8/23/2006 | 8/23/2006 | 8/23/2006 12:59:12 PM | P | PASS |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley t/s u/g new ok
|
ELE06-02443
| Final | 8/23/2006 | 8/23/2006 | 8/23/2006 12:26:12 PM | P | PASS |
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
|
ELE06-03137
| Rough-In Permanent Service | 8/23/2006 | 8/23/2006 | 8/23/2006 10:31:52 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson no p/s corr. needs 1/0 cu. 3/0 alum. to bond water 250.66, 250.64(C) shall not splice GEC, r/i ok survey for nail plates called
|
ELE06-02515
| Final | 8/22/2006 | 8/23/2006 | 8/23/2006 9:43:23 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok no card
|
ELE06-00165
| Final | 8/22/2006 | 8/23/2006 | 8/23/2006 9:42:50 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok called needs labels for both p/s, bond H&C water no card
|
ELE06-03090
| Final | 8/21/2006 | 8/23/2006 | 8/23/2006 9:14:19 AM | A | FAIL |
|
|
jessica - call 1/2 hr prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 230.28 needs stiff let to oppose strain not guy kit, 110.3(B) use manufactures breakers only, 250.64(B) protect #8 GEC or install #6, 250.52(A)(1)or104(A)(1) grd or bond water system corr. called
|
ELE06-01236
| Final | 8/21/2006 | 8/23/2006 | 8/23/2006 8:17:36 AM | A | FAIL |
|
|
if locked the key is on top of the furnace behind the vent; Phone #: ###-#### Internet Inspection Request from: steve creswell corr. called left message, 410.8 clearence MB closet fixture, 408.4 panel directory
|