Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC06-02060 MEC-Aging Inspection8/23/20068/23/20068/28/2006 5:54:25 PM PEND
i called jay and left a message to call me about the staus of this permit. this should have been grouped to a building permit.
MEC06-02747 Rough-in8/22/20068/23/20068/23/2006 5:03:46 PMAPEND
Need inspect on piping to 10 boilers with radiant piping- Call scott with questions @ ###-####. Thanks!; Phone #: ###-#### Internet Inspection Request from: Kelea Allen..i called scott and told him this permit is grouped to a bldg permit for s/f dwelling. he will call and get the correct bldg permit and then re-call for the inspection
MEC06-02749 Final8/23/20068/23/20068/23/2006 5:02:06 PMPPART
contact patrick @ 8711259 if there are any questions; Phone #: ###-#### Internet Inspection Request from: PATRICK FLEMING...20lb gas test ok..need to complete flue, combustion air, either insulate the duct or make it a conditioned space..thanks
MEC06-02279 Rough-in8/23/20068/23/20068/23/2006 4:26:39 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS..filter access to be readily accessible..need 1" clearance around b-vents..tape or seal all metal duct joints..need to fire caulk all flue penetrations..i spoke to troy about all of these issues
MEC06-02494 Final8/23/20068/23/20068/23/2006 3:47:08 PMPPASS
Phone #: ###-#### Internet Inspection Request from: william kerwin
MEC06-02437 Final8/23/20068/23/20068/23/2006 3:08:12 PMPPASS
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
MEC06-02693 Final8/23/20068/23/20068/23/2006 2:04:54 PMPPASS
frank ###-####
MEC06-01802 Final8/23/20068/23/20068/23/2006 1:50:16 PMPFAIL
Please inspect by 3:30, all contractors will be gone after that and there will be no access. Thanks. April.; Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS...need to move filter access
MEC06-02279 Pressure Test8/23/20068/23/20068/23/2006 1:32:20 PMPPASS
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS...20lb test on all units ok
MEC06-02742 Pressure Test8/22/20068/23/20068/23/2006 1:05:22 PMAFAIL
jd ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley..i put a stop work on this job. the owner or general contractor needs a building permit. once this has been done, i can do your inspection. thanks dixie
MEC06-02693 Pressure Test8/22/20068/23/20068/23/2006 1:04:06 PMAPASS
frank; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles..20lb ok
MEC06-02001 MEC-Aging Inspection8/23/20068/23/20068/23/2006 12:51:49 PM PASS
work still in progress
MEC06-02511 Rough-in8/22/20068/23/20068/23/2006 11:43:45 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS..OH OH..ALEX WAS WAITING FOR FRAMER TO FINISH AN AREA SO HE COULD COMPLETE HIS R/A..I THINK HE FORGOT ABOUT IT. RE-CALL WHEN DONE..PLEASE CALL ME APRIL...THANKS DIXIE
MEC06-02511 Pressure Test8/22/20068/23/20068/23/2006 11:41:45 AMAPASS
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS...60LB TEST OK
MEC06-02536 Pressure Test8/22/20068/23/20068/23/2006 11:06:40 AMADEFR
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS..OOPS WRONG BUILDING
MEC06-02536 Rough-in8/22/20068/23/20068/23/2006 11:06:04 AMADEFR
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS...THIS IS THE WRONG BUILDING..HA HA
MEC06-02553 Final8/16/20068/23/20068/23/2006 10:22:20 AMAPASS
Please call Clay when on your way at ###-####. Thanks, Andrea.; Phone #: ###-#### Internet Inspection Request from: Andrea Creek
MEC06-02553 Pressure Test8/16/20068/23/20068/23/2006 10:21:56 AMAPASS
Please call Clay when on your way at ###-####. Thanks, Andrea.; Phone #: ###-#### Internet Inspection Request from: Andrea Creek...20LB OK
MEC06-02511 Conference8/22/20068/23/20068/22/2006 3:58:14 PMACANC
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS Inspection cancelled from web by: APRIL THOMAS