ELE07-01308
| Conference | 8/23/2007 | 8/23/2007 | 8/23/2007 3:23:12 PM | P | DONE |
|
|
talked with contr about 312,6 and 314,28
|
ELE06-03221
| Final | 8/23/2007 | 8/23/2007 | 8/23/2007 2:51:02 PM | P | PASS |
|
|
final for permit owner secured elect contr. to take over job
|
ELE07-02651
| Final | 8/23/2007 | 8/23/2007 | 8/23/2007 2:10:34 PM | P | PASS |
|
|
JEFF Phone #: ###-#### ok see added p/s no card at site builder has it
|
ELE07-02652
| Final | 8/23/2007 | 8/23/2007 | 8/23/2007 2:08:48 PM | P | PASS |
|
|
JEFF Phone #: ###-#### nOTE: PLEASE CALL 10 MIN PRIOR TO INSPECTION TO MEET ok see added p/s ok no card at site, builder has it
|
ELE07-02652
| Permanent Service | 8/23/2007 | 8/23/2007 | 8/23/2007 2:07:49 PM | P | PASS |
|
|
JEFF Phone #: ###-#### nOTE: PLEASE CALL 10 MIN PRIOR TO INSPECTION TO MEET p/s u/g new ok
|
ELE07-02651
| Permanent Service | 8/23/2007 | 8/23/2007 | 8/23/2007 2:00:05 PM | P | PASS |
|
|
JEFF Phone #: ###-#### p/s u/g new ok
|
ELE07-02923
| Final | 8/23/2007 | 8/23/2007 | 8/23/2007 12:49:48 PM | P | FAIL |
|
|
Pat Gill contact or Roger Reynolds ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis see added r/i
|
ELE07-02923
| Electrical Rough-In | 8/23/2007 | 8/23/2007 | 8/23/2007 12:49:21 PM | P | FAIL |
|
|
Pat Gill contact or Roger Reynolds ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis corr, 400.8(5) no cords allowed above ceilings, all for exam rm shall meet 517.13 a&b no flex for branch circuits feeding exam rm
|
ELE07-01308
| Electrical Rough-In | 8/21/2007 | 8/23/2007 | 8/23/2007 11:39:00 AM | A | PART |
|
|
Please inspect for rough-in and service connect. Call Brian for any questions ###-#### Phone #: ###-#### Internet Inspection Request from: Margaret Roye SE corner tennant and rest rms walls ok corrections at service grd to metal too small and 314.28
|
ELE07-01598
| Permanent Service | 8/22/2007 | 8/23/2007 | 8/23/2007 10:57:38 AM | A | FAIL |
|
|
wayne Phone #: ###-####Note: main gear east elevator corr grd water within 5ft needs bell ends for u/g pvc, plastic or listed conn for GEC, terminate all GEC to neutral bus
|
ELE07-01598
| Electrical Rough-In | 8/23/2007 | 8/23/2007 | 8/23/2007 10:54:56 AM | A | PART |
|
|
wayne Phone #: ###-####Note: main gear east elevator walls and hard ceilings elevator rm
|
ELE07-01885
| ELE-Aging Inspection | 8/23/2007 | 8/23/2007 | 8/23/2007 10:10:18 AM | | CANC |
|
|
|
ELE07-01864
| ELE-Aging Inspection | 8/23/2007 | 8/23/2007 | 8/23/2007 10:10:09 AM | | CANC |
|
|
|
ELE07-02529
| Electrical Rough-In | 8/22/2007 | 8/23/2007 | 8/23/2007 10:07:46 AM | A | PART |
|
|
Tim, east stairwell only; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok
|
ELE07-02882
| Final | 8/22/2007 | 8/23/2007 | 8/23/2007 9:37:08 AM | A | PASS |
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
|
ELE07-02913
| Electrical Rough-In | 8/21/2007 | 8/23/2007 | 8/23/2007 9:09:37 AM | A | PASS |
|
|
Ready for final inspection. Coriann will meet you at suite #175 to let you in if you would please call her cell ###-####. Call Dan with any questions. Thanks! Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|
ELE07-02913
| Final | 8/23/2007 | 8/23/2007 | 8/23/2007 9:08:52 AM | A | PASS |
|
|
Ready for final inspection. Coriann will meet you at suite #175 to let you in if you would please call her cell ###-####. Call Dan with any questions. Thanks! Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
|
ELE07-02629
| Final | 8/21/2007 | 8/23/2007 | 8/23/2007 8:27:17 AM | A | PASS |
|
|
mitch Phone #: ###-#### called needs outside fixture installed ok
|
ELE07-02636
| Final | 8/22/2007 | 8/23/2007 | 8/22/2007 3:57:10 PM | A | PASS |
|
|
andy Phone #: ###-#### ok card signed
|
ELE07-02788
| Electrical Rough-In | 8/22/2007 | 8/23/2007 | 8/22/2007 2:15:26 PM | A | PART |
|
|
corey Note: swimming pool underground Phone #: ###-#### u/g for pool sub panel ok
|
ELE07-02922
| Permanent Service | 8/22/2007 | 8/23/2007 | 8/22/2007 2:14:24 PM | A | PASS |
|
|
corey Phone #: ###-#### needs #4 GEC and water bond, remove cable box from below service p/s u/g rec. ok
|