Inspections for the day of: Tuesday, August 23, 2011.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00348 INSP-Sprinkler Rough-in8/23/20118/23/20118/25/2011 4:18:54 PMPPART
Spacing at the reception area and back hall in need of adjustment. Remainder of overhead work approved for cover.
FIR11-00241 INSP-Sprinkler Rough-in8/23/20118/23/20118/25/2011 4:16:06 PMPPART
FIR11-00343 INSP-Final Inspection8/23/20118/23/20118/25/2011 4:15:33 PMPNR
FIR08-00239 INSP-Sprinkler Rough-in/Hydro8/22/20118/23/20118/25/2011 4:10:33 PMAPART
Pneumatic testing for the two basement dry systems, dry standpipe, and both buildings #2 and #3 2nd and 4th floor level dry systems completed satisfactory per NFPA 13 requirements.