Inspections for the day of: Tuesday, August 23, 2011.
Number of inspections: 11
Percentage of inspections complete: 91 %
Percentage of inspections not complete: 9 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-00610 FIRE-Conference8/17/20118/22/2011 A 
Troy-call Dixie for am meeting
FIR11-00159 INSP-Final Inspection8/22/20118/23/20118/23/2011 3:08:16 PMAFAIL
Todays inspection was for the duct smoke detector shutdown which passed.
BLD11-01437 FIRE-Final Inspection8/22/20118/23/20118/23/2011 3:04:47 PMPPASS
life safety passed
FIR11-00415 INSP-Final Inspection8/22/20118/23/20118/23/2011 2:29:12 PMAPASS
permit finaled
BLD11-00263 FIRE-Final Inspection8/23/20118/23/20118/23/2011 2:24:50 PMAFAIL
Life / Safety will be ok to pass when a permit for the duct smoke detector/hvac shutdown has been issued and passed.
BLD11-01797 FIRE-Final Inspection8/23/20118/23/20118/23/2011 2:23:00 PMPFAIL
Provide floor plan that matches the actual wall layout and remove the thumbturn lock and provide single action hardware on the west exit door.
FIR11-00239 INSP-Final Inspection8/23/20118/23/20118/23/2011 2:02:58 PMPFAIL
Left voice message 30 minute before arrival. Stopped at job site but nobody knew anything about the inspection. No inspection was performed.
FIR11-00371 INSP-Sprinkler Rough-in8/22/20118/23/20118/23/2011 11:38:16 AMAPASS
See the city approved plans for locations where the sprinkler piping is ok to cover. Todays area was in the south east corner of the building. One head, as marked on the plans, needs to be relocated or another pendant added due to a soffit obstruction.
BLD11-01801 FIRE-Final Inspection8/22/20118/23/20118/23/2011 11:34:29 AMAPASS
Life safety passed. Andrea was going to have the next door locksmith remove the thumbturn deadbolt and replace it with keyed on the egress side before the building inspector arrives.
FIR11-00334 INSP-Sprinkler Rough-in8/22/20118/23/20118/23/2011 11:17:46 AMAPASS
The sprinkler piping in the master bath can now be covered. I let the sprinkler contractor know that the outside alarm bell can not be installed where the builder currently has it located. It needs to be located on the front of the house or relocated to the east end of the house which is closer to the street. Tim Frost was going to contact the builder and let him know this same information.
BLD11-01966 FIRE-Final Inspection8/22/20118/23/20118/23/2011 11:14:30 AMAFAIL
Provide annual inspection for the fire sprinkler system. Repair the Comm troubles on the fire alarm panel. Repair the two emergency lights and one exit sign at the north end of the tenant space.