BLD15-00802
| FIRE-Final Inspection | 8/23/2016 | 8/23/2016 | 8/23/2016 3:24:01 PM | P | FAIL |
|
|
City approved drawings with small documentation not on site at time of inspection, city approved drawings and small documentation need to be onsite for inspection. Need to have signage installed for no parking fire lane, no signage installed at time of inspection. Need to verify if the 3 new structures (two covered outdoor seating area's and one restroom building) require fire extinguishers, based on labeled occupancy type of A3 and B fire extinguishers should be installed for each structure.
|
FIR16-00155
| INSP-Sprinkler Rough-in | 8/23/2016 | 8/23/2016 | 8/23/2016 2:00:26 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping located on level 4 complete, overhead fire sprinkler piping located on level 4 of the clearwater building approved for cover.
|
FIR15-00727
| INSP-Sprinkler Rough-in | 8/23/2016 | 8/23/2016 | 8/23/2016 1:58:32 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping located above the ceiling grid in ballroom Section A complete, overhead fire sprinkler in ballroom Section A approved for cover. Rough to cover inspection for overhead fire sprinkler piping located in level 4 escalator lobby complete, overhead fire sprinkler piping located above the hardlids on level 4 escalator lobby approved for cover.
|
BLD16-01908
| FIRE-Final Inspection | 8/23/2016 | 8/23/2016 | 8/23/2016 11:09:49 AM | P | PART |
|
|
No fire sprinkler modifications with this space, (When dividing wall is removed between the 2 existing space fire sprinkler work will be required) no fire alarms, fire extinguisher is in place with current inspection tag. Exit lights/ exit egress discharge lighting was not installed at time of inspection, exit signs and exit dicharge will be installed and a new inspection request will be generated.
|
BLD16-03073
| FIRE-Final Inspection | 8/23/2016 | 8/23/2016 | 8/23/2016 10:29:46 AM | P | PASS |
|
|
No fire sprinklers, no fire alarms, discussed location for fire extinguisher to be mounted, noted that the existing door hardware is round type door handle with keyed deadbolt. Final life fire sfatey inspection passed/complete
|
BLD16-02360
| FIRE-Final Inspection | 8/22/2016 | 8/23/2016 | 8/23/2016 10:14:52 AM | A | CANC |
|
|
Spoke with point of contact, John Phone #: ###-####, tenant space is not ready for final life fire safety inspection, this inspection request cancelled per conversation with John and a new inspection request will be scheduled for a later date.
|
BLD14-03039
| FIRE-Final Inspection | 8/22/2016 | 8/23/2016 | 8/23/2016 10:01:34 AM | A | PART |
|
|
Spoke with point of contact, Jay Phone #: ###-####, discussed location for fire alarm document cabinet in fire sprinkler riser room. Jay is requesting a partial final for exterior life fire safety, property has an active fire sprinkler system, property has an active fire panel, final inspection is for exterior no fire extinguishers are required for exterior. Temporary construction fencing in place at time of inspection which cannot stay in place when property is occupied. When building becomes occupied the fencing needs to be removed or a gate with impact/single action hardware will need to be installed. Partial fire life safety final inspection for exterior passed/complete
|
FIR16-00494
| INSP-Sprinkler Rough-in | 8/22/2016 | 8/23/2016 | 8/23/2016 9:27:08 AM | A | PASS |
|
|
FInal inspection for underground piping that is installed passed/complete, underground supply approved for cover.
|
BLD14-01868
| FIRE-Final Inspection | 8/22/2016 | 8/23/2016 | 8/23/2016 9:26:21 AM | A | CANC |
|
|
Spoke with people inside at tenant space, none of the individuals I talked to had any information for a final fire inspection request. No phone name or phone number provided for contact information. Inspection request will need to be rescheduled for another day.
|
FIR16-00520
| INSP-Sprinkler Rough-in | 8/22/2016 | 8/23/2016 | 8/22/2016 2:32:02 PM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping per this area of work approved for cover.
|
FIR16-00028
| INSP-Sprinkler Rough-in/Hydro | 8/22/2016 | 8/23/2016 | 8/22/2016 2:10:16 PM | A | CANC |
|
|
Please call Anthony when heading out, thank you! Reminder, standpipes and overhead were on two separate permits, both have been scheduled for final. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|