Inspections for the day of: Tuesday, August 23, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-00802 FIRE-Final Inspection8/23/20168/23/20168/23/2016 3:24:01 PMPFAIL
City approved drawings with small documentation not on site at time of inspection, city approved drawings and small documentation need to be onsite for inspection. Need to have signage installed for no parking fire lane, no signage installed at time of inspection. Need to verify if the 3 new structures (two covered outdoor seating area's and one restroom building) require fire extinguishers, based on labeled occupancy type of A3 and B fire extinguishers should be installed for each structure.
FIR16-00155 INSP-Sprinkler Rough-in8/23/20168/23/20168/23/2016 2:00:26 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping located on level 4 complete, overhead fire sprinkler piping located on level 4 of the clearwater building approved for cover.
FIR15-00727 INSP-Sprinkler Rough-in8/23/20168/23/20168/23/2016 1:58:32 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping located above the ceiling grid in ballroom Section A complete, overhead fire sprinkler in ballroom Section A approved for cover. Rough to cover inspection for overhead fire sprinkler piping located in level 4 escalator lobby complete, overhead fire sprinkler piping located above the hardlids on level 4 escalator lobby approved for cover.
BLD16-01908 FIRE-Final Inspection8/23/20168/23/20168/23/2016 11:09:49 AMPPART
No fire sprinkler modifications with this space, (When dividing wall is removed between the 2 existing space fire sprinkler work will be required) no fire alarms, fire extinguisher is in place with current inspection tag. Exit lights/ exit egress discharge lighting was not installed at time of inspection, exit signs and exit dicharge will be installed and a new inspection request will be generated.
BLD16-03073 FIRE-Final Inspection8/23/20168/23/20168/23/2016 10:29:46 AMPPASS
No fire sprinklers, no fire alarms, discussed location for fire extinguisher to be mounted, noted that the existing door hardware is round type door handle with keyed deadbolt. Final life fire sfatey inspection passed/complete
BLD16-02360 FIRE-Final Inspection8/22/20168/23/20168/23/2016 10:14:52 AMACANC
Spoke with point of contact, John Phone #: ###-####, tenant space is not ready for final life fire safety inspection, this inspection request cancelled per conversation with John and a new inspection request will be scheduled for a later date.
BLD14-03039 FIRE-Final Inspection8/22/20168/23/20168/23/2016 10:01:34 AMAPART
Spoke with point of contact, Jay Phone #: ###-####, discussed location for fire alarm document cabinet in fire sprinkler riser room. Jay is requesting a partial final for exterior life fire safety, property has an active fire sprinkler system, property has an active fire panel, final inspection is for exterior no fire extinguishers are required for exterior. Temporary construction fencing in place at time of inspection which cannot stay in place when property is occupied. When building becomes occupied the fencing needs to be removed or a gate with impact/single action hardware will need to be installed. Partial fire life safety final inspection for exterior passed/complete
FIR16-00494 INSP-Sprinkler Rough-in8/22/20168/23/20168/23/2016 9:27:08 AMAPASS
FInal inspection for underground piping that is installed passed/complete, underground supply approved for cover.
BLD14-01868 FIRE-Final Inspection8/22/20168/23/20168/23/2016 9:26:21 AMACANC
Spoke with people inside at tenant space, none of the individuals I talked to had any information for a final fire inspection request. No phone name or phone number provided for contact information. Inspection request will need to be rescheduled for another day.
FIR16-00520 INSP-Sprinkler Rough-in8/22/20168/23/20168/22/2016 2:32:02 PMAPASS
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping per this area of work approved for cover.
FIR16-00028 INSP-Sprinkler Rough-in/Hydro8/22/20168/23/20168/22/2016 2:10:16 PMACANC
Please call Anthony when heading out, thank you! Reminder, standpipes and overhead were on two separate permits, both have been scheduled for final. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello