Inspections for the day of: Wednesday, August 23, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02099 Conference8/23/20178/23/20178/23/2017 2:38:12 PMPDONE
Harlan-please call 15 minutes prior to meet Phone #: ###-####
Discussed wiring for detached garage with unfinished walls and 100amp feed.
1 outdoor light at each man door controlled by switch or automatic means, minimum of 2 receptacles for car bays for depth, all 120 volt receptacle outlets shal be 20 amp, tamper resistant, GFCI protected and wiring shall be protected from physical damage by wiring meathod or framing if MN cable. Minimum of #4 for garage feeders with #6 ground and 2 ground rods at garage. Depth of underground shall be 18" for conduit or 24" for cable.
ELE17-01337 Conference8/23/20178/23/20178/23/2017 1:59:03 PMPDONE
We are requesting a consult with the inspector to discuss what we need to do to run romex before roof is on for this afternoon. Our contact is Rick @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate
334.12- NM cable shall not be installed in a wet or damp location. If installed and becomes wet or damp it shall be replaced.
ELE17-01549 Electrical Rough-In8/22/20178/23/20178/23/2017 1:12:16 PMPPASS
Shane is the contact his cell no. is 208.697.1925 Phone #: ###-#### Inspection requested via web by Shawna Gates
1 of many South band light pour rough in ok cover
ELE17-02133 Electrical Rough-In8/22/20178/23/20178/23/2017 11:22:00 AMAPASS
Please call Sid w/any questions @ ###-####

This is for a ceiling inspection

Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Grid rough in ok cover
ELE17-00811 Electrical Rough-In8/22/20178/23/20178/23/2017 10:39:43 AMAPASS
Please call ###-#### before going to job to inspect. Would like Journeyman on job to go over job with inspector. Phone #: ###-#### Inspection requested via web by Zane Robertson
Confusion created due to miss edit. Last rough in shown as a cancel with note of rough in ok cover.
Halls and bathrooms rough walls and hardlids rough in ok cover
ELE17-02577 Electrical Rough-In8/22/20178/23/20178/23/2017 10:08:02 AMAPASS
Phone #: ###-#### Inspection requested via web by kendall bender
East demizing wall only rough in ok cover
ELE17-01935 Electrical Rough-In8/22/20178/23/20178/23/2017 9:40:33 AMAPASS
Von. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Discussed 300.4(E)- IMC minimum required where raceway is installed with in 1 1/2" of lowest part of roof deck. Also building steel shall be included as part of grounding electrode system. Bath walls and hardlids only rough in ok cover
ELE17-02026 Final8/23/20178/23/20178/23/2017 8:47:44 AMAFAIL
Phone #: ###-#### Inspection requested via web by Bob Glenn
410.16- Luminaires in cloths closet shall have totally enclosed bulbs.
ELE17-02266 Final8/23/20178/23/20178/23/2017 8:25:26 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok