ELE01-02712
| Final | 8/21/2001 | 8/24/2001 | 8/24/2001 12:00:00 AM | A | NH |
|
|
Scheduled by a contractor via Hello! on 08/21/2001 at 22:44:05. Contact: ###-####. called got mach. 8/24/2001 9:15:13 AM
|
ELE01-02959
| Electrical Rough-In | 8/23/2001 | 8/24/2001 | 8/24/2001 12:00:00 AM | A | PASS |
|
|
###-#### john
|
ELE01-02784
| Electrical Rough-In | 8/23/2001 | 8/24/2001 | 8/24/2001 12:00:00 AM | A | PART |
|
|
JIM ###-#### R/I electrode ok to cover 8/24/2001 11:58:22 AM
|
ELE01-02684
| Electrical Rough-In | 8/23/2001 | 8/24/2001 | 8/24/2001 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 08/23/2001 at 16:46:44. Contact: ###-####. 1st R/i ok 8/24/2001 11:58:39 AM
|
ELE01-02137
| Electrical Rough-In | 8/24/2001 | 8/24/2001 | 8/24/2001 12:00:00 AM | P | PASS |
|
|
###-#### roger
|
ELE01-01987
| Electrical Rough-In | 8/24/2001 | 8/24/2001 | 8/24/2001 12:00:00 AM | P | FAIL |
|
|
ceiling cover- wayne ###-#### Equipment grounds not connected to boxes as required by 250-148 must have all boxes opened for inspection too much bend in flexes broken flex and reducing washers 8/24/2001 2:21:22 PM 8/24/2001 2:34:01 PM
|
ELE01-02966
| Final | 8/24/2001 | 8/24/2001 | 8/24/2001 12:00:00 AM | P | PASS |
|
|
fn dave ###-####
|
ELE01-02970
| Electrical Rough-In | 8/24/2001 | 8/24/2001 | 8/24/2001 12:00:00 AM | P | PART |
|
|
###-#### r/i -shawn wall ok 8/24/2001 5:09:52 PM
|
ELE01-02712
| Final | 8/24/2001 | 8/24/2001 | 8/24/2001 12:00:00 AM | P | FAIL |
|
|
Added by Inspector: 336 On 8/24/2001 12:21:13 PM grounding and KO seals
|
ELE01-01470
| Electrical Rough-In | 8/23/2001 | 8/24/2001 | 8/24/2001 12:00:00 AM | P | FAIL |
|
|
###-####- JOHN box fill circuiting and protection 8/24/2001 3:33:48 PM
|