ELE05-03094
| Rough-In Permanent Service | 8/24/2005 | 8/24/2005 | 8/24/2005 4:10:39 PM | P | PART |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Barbara Moore u/g ok
|
ELE05-03082
| Electrical Rough-In | 8/23/2005 | 8/24/2005 | 8/24/2005 3:23:03 PM | P | PART |
|
|
Please inspect ground, uffer and footing sleeves. Thanks!; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney ok
|
ELE05-01702
| Final | 8/24/2005 | 8/24/2005 | 8/24/2005 3:00:36 PM | P | PASS |
|
|
pat Note: please call 1/2 hr prior to inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE05-02974
| Temporary Service | 8/24/2005 | 8/24/2005 | 8/24/2005 2:17:49 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 8/24/2005 at 8:13:25 AM. Contact: ###-####. t/s u/g new ok
|
ELE05-02905
| Electrical Rough-In | 8/24/2005 | 8/24/2005 | 8/24/2005 1:51:10 PM | P | NR |
|
|
pat Note: please call 1/2 hr prior to inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles owner needs bld, mech,plm permits, Tom A posted stop work at job site
|
ELE05-03038
| Permanent Service | 8/22/2005 | 8/24/2005 | 8/24/2005 12:24:19 PM | P | FAIL |
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted met contractor, 110.14 loose grd connections, 250.66 bonding jumper needs to 1/0,250.70 use grd clamps listed for wire size, 250.64 remove GEC from feeder conduit
|
ELE05-02335
| Final | 8/23/2005 | 8/24/2005 | 8/24/2005 9:44:58 AM | A | FAIL |
|
|
Internet Inspection Request from: Radon Elaina could not locate
|
ELE04-04122
| Electrical Rough-In | 8/23/2005 | 8/24/2005 | 8/24/2005 9:27:17 AM | A | PASS |
|
|
Contact is Steve Sellers. Trench inspection prior to cover.; Phone #: ###-#### Internet Inspection Request from: Samantha Patterson u/g ok verified depth with meter
|
ELE05-02148
| Final | 8/23/2005 | 8/24/2005 | 8/24/2005 9:12:04 AM | A | FAIL |
|
|
Internet Inspection Request from: Radon Elaina cor. posted called 110.3 useing flex fittings on emt, 352.24 pvc damaged, 352.46&300.12 raceway shall terminate to sign cabinet, this job is a mess
|
ELE05-01789
| DOC - Permit Finaled | 8/24/2005 | 8/24/2005 | 8/24/2005 12:00:00 AM | A | PASS |
|
|
|
ELE05-02335
| DOC - Permit Expired | 8/24/2005 | 8/24/2005 | 8/24/2005 12:00:00 AM | A | PASS |
|
|
Internet Inspection Request from: Radon Elaina could not locate noone at site no what sign
|
ELE05-01748
| DOC - Permit Expired | 8/24/2005 | 8/24/2005 | 8/24/2005 12:00:00 AM | P | PASS |
|
|
|