Inspections for the day of: Wednesday, August 24, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03094 Rough-In Permanent Service8/24/20058/24/20058/24/2005 4:10:39 PMPPART
chris; Phone #: ###-#### Internet Inspection Request from: Barbara Moore u/g ok
ELE05-03082 Electrical Rough-In8/23/20058/24/20058/24/2005 3:23:03 PMPPART
Please inspect ground, uffer and footing sleeves. Thanks!; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney ok
ELE05-01702 Final8/24/20058/24/20058/24/2005 3:00:36 PMPPASS
pat Note: please call 1/2 hr prior to inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE05-02974 Temporary Service8/24/20058/24/20058/24/2005 2:17:49 PMPPASS
Scheduled by a contractor via Hello! on 8/24/2005 at 8:13:25 AM. Contact: ###-####. t/s u/g new ok
ELE05-02905 Electrical Rough-In8/24/20058/24/20058/24/2005 1:51:10 PMPNR
pat Note: please call 1/2 hr prior to inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles owner needs bld, mech,plm permits, Tom A posted stop work at job site
ELE05-03038 Permanent Service8/22/20058/24/20058/24/2005 12:24:19 PMPFAIL
jerry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted met contractor, 110.14 loose grd connections, 250.66 bonding jumper needs to 1/0,250.70 use grd clamps listed for wire size, 250.64 remove GEC from feeder conduit
ELE05-02335 Final8/23/20058/24/20058/24/2005 9:44:58 AMAFAIL
Internet Inspection Request from: Radon Elaina could not locate
ELE04-04122 Electrical Rough-In8/23/20058/24/20058/24/2005 9:27:17 AMAPASS
Contact is Steve Sellers. Trench inspection prior to cover.; Phone #: ###-#### Internet Inspection Request from: Samantha Patterson u/g ok verified depth with meter
ELE05-02148 Final8/23/20058/24/20058/24/2005 9:12:04 AMAFAIL
Internet Inspection Request from: Radon Elaina cor. posted called 110.3 useing flex fittings on emt, 352.24 pvc damaged, 352.46&300.12 raceway shall terminate to sign cabinet, this job is a mess
ELE05-01789 DOC - Permit Finaled8/24/20058/24/20058/24/2005 12:00:00 AMAPASS
ELE05-02335 DOC - Permit Expired8/24/20058/24/20058/24/2005 12:00:00 AMAPASS
Internet Inspection Request from: Radon Elaina could not locate noone at site no what sign
ELE05-01748 DOC - Permit Expired8/24/20058/24/20058/24/2005 12:00:00 AMPPASS