FIR05-00266
| INSP-Sprinkler Rough-in | 8/16/2005 | 8/17/2005 | | A | |
|
|
###-#### - bruce Note: after morning 9:00 ish
|
FIR05-00266
| INSP-Sprinkler Rough-in | 8/24/2005 | 8/24/2005 | 8/24/2005 4:55:39 PM | P | PART |
|
|
Underground fire supply line stub out to 8' of building is good for cover.
|
FIR04-00684
| INSP-Sprinkler Rough-in/Hydro | 8/24/2005 | 8/24/2005 | 8/24/2005 3:21:26 PM | P | PART |
|
|
Overhead rough-in for the basement area from column lines 3 through 14 on the west side of the corridor as marked on sheet FP2 of the approved plans is acceptable to cover.
|
BLD05-00236
| FIRE-Final Inspection | 8/23/2005 | 8/24/2005 | 8/24/2005 11:22:52 AM | A | PASS |
|
|
Fire life safety passed inspection.
|
BLD05-00277
| FIRE-Final Inspection | 8/23/2005 | 8/24/2005 | 8/24/2005 10:09:20 AM | A | PART |
|
|
Final pending verification of plan review approval for keyed locking door hardware at tenant shared restroom access doors.
|
MIS04-00266
| FIR-Final | 8/19/2005 | 8/24/2005 | 8/24/2005 9:23:13 AM | A | PASS |
|
|
Life safety acceptable.
|
FIR05-00259
| INSP-Sprinkler Rough-in/Hydro | 8/24/2005 | 8/24/2005 | 8/24/2005 12:00:00 AM | P | PART |
|
|
Dry system 24 hour air test passed with the maximum allowable loss of 1.5 psi, air pressure at 2:00 p.m 8/24/05 was 40.5 psi.
|
MIS05-00125
| FIR-Final | 8/17/2005 | 8/24/2005 | 8/23/2005 1:53:35 PM | A | CANC |
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Inspection cancelled from web by: Marsha Smylie
|