Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00266 INSP-Sprinkler Rough-in8/16/20058/17/2005 A 
###-#### - bruce Note: after morning 9:00 ish
FIR05-00266 INSP-Sprinkler Rough-in8/24/20058/24/20058/24/2005 4:55:39 PMPPART
Underground fire supply line stub out to 8' of building is good for cover.
FIR04-00684 INSP-Sprinkler Rough-in/Hydro8/24/20058/24/20058/24/2005 3:21:26 PMPPART
Overhead rough-in for the basement area from column lines 3 through 14 on the west side of the corridor as marked on sheet FP2 of the approved plans is acceptable to cover.
BLD05-00236 FIRE-Final Inspection8/23/20058/24/20058/24/2005 11:22:52 AMAPASS
Fire life safety passed inspection.
BLD05-00277 FIRE-Final Inspection8/23/20058/24/20058/24/2005 10:09:20 AMAPART
Final pending verification of plan review approval for keyed locking door hardware at tenant shared restroom access doors.
MIS04-00266 FIR-Final8/19/20058/24/20058/24/2005 9:23:13 AMAPASS
Life safety acceptable.
FIR05-00259 INSP-Sprinkler Rough-in/Hydro8/24/20058/24/20058/24/2005 12:00:00 AMPPART
Dry system 24 hour air test passed with the maximum allowable loss of 1.5 psi, air pressure at 2:00 p.m 8/24/05 was 40.5 psi.
MIS05-00125 FIR-Final8/17/20058/24/20058/23/2005 1:53:35 PMACANC
randy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Inspection cancelled from web by: Marsha Smylie