Inspections for the day of: Thursday, August 24, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01740 ELE-Aging Inspection8/24/20068/24/20068/25/2006 7:49:44 AM CANC
ELE06-03170 Final8/24/20068/24/20068/24/2006 2:49:56 PMPPASS
pat; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
ELE06-03155 Final8/23/20068/24/20068/24/2006 2:10:31 PMPFAIL
Inspect service, A/C, and outlets. Work performed by Tony Norton.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz corr. called 200.6 shall not ID 6 or smaller neutral, 210.63 gfci recept outside for a/c, 408.6 label panel, note remove old GEC from j box, update permit for a/c p/s and 2 rms, and call for r/i p/s not final
ELE06-02282 Final8/24/20068/24/20068/24/2006 12:54:27 PMPPASS
hz; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
ELE06-01753 Final8/23/20068/24/20068/24/2006 11:04:57 AMAPASS
rick; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
ELE06-03154 Rough-In Permanent Service8/23/20068/24/20068/24/2006 10:30:29 AMAPASS
rick; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley r/i p/s o/h new ok
ELE06-02893 Temporary Service8/23/20068/24/20068/24/2006 9:54:00 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Jari Rivers corr. fee due called 312.5, 250.64(E) use plastic conn or listed grd conn for GEC, 250.53(G) shall install grd rod as code noted states, 110.12(C) clean dirt from t/s removed conn left in t/s on hot lugs
ELE06-02020 Electrical Rough-In8/23/20068/24/20068/24/2006 9:34:21 AMAFAIL
Eric; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections not made called still needs nail plates, and use listed conn. for low voltage cable not emt conn.
ELE06-00460 Permanent Service8/23/20068/24/20068/24/2006 8:58:15 AMAPASS
duke; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
p/s u/g new ok for house meter
ELE06-00117 Electrical Rough-In8/23/20068/24/20068/24/2006 8:47:06 AMAPART
mike - ceiling; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
N W ceiling areas ok
ELE06-02811 Electrical Rough-In8/23/20068/24/20068/24/2006 8:23:33 AMAPASS
whitney; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok