ELE06-02316
| ELE-Aging Inspection | 8/24/2006 | 8/24/2006 | 8/24/2006 4:18:39 PM | | DONE |
|
|
called, left message to call for final
|
ELE06-03153
| Temporary Service | 8/24/2006 | 8/24/2006 | 8/24/2006 3:47:25 PM | P | PASS |
|
|
shawn; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s o/h n ok
|
ELE06-02929
| Rough-In Permanent Service | 8/24/2006 | 8/24/2006 | 8/24/2006 3:17:43 PM | P | PASS |
|
|
joe; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made ric ok, p/s u/g n ok
|
ELE06-03160
| Permanent Service | 8/24/2006 | 8/24/2006 | 8/24/2006 2:04:19 PM | P | FAIL |
|
|
Inspection for Afternoon. Thank you!; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contr, left corr notice, nec 230.24(A)exc3, bottom of drip loop shall be min 18" above roof line, 250.52(A)(3) and BCC concrete encased electrode shall be installed
|
ELE06-03168
| Rough-In Permanent Service | 8/24/2006 | 8/24/2006 | 8/24/2006 1:12:01 PM | P | CANC |
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see ri
|
ELE06-03168
| Electrical Rough-In | 8/24/2006 | 8/24/2006 | 8/24/2006 1:11:37 PM | P | PASS |
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to pour gec, ric ok, need to see gec before backfill
|
ELE06-02278
| Final | 8/23/2006 | 8/24/2006 | 8/24/2006 11:48:25 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl ok to final
|
ELE06-02144
| Final | 8/23/2006 | 8/24/2006 | 8/24/2006 10:35:35 AM | A | PASS |
|
|
call for code; Phone #: ###-#### Internet Inspection Request from: Dan Rohl ok to final
|
ELE06-03151
| Permanent Service | 8/23/2006 | 8/24/2006 | 8/24/2006 10:20:40 AM | A | PASS |
|
|
please call prior to inspection///###-#### pat p/s u/g rec ok
|
ELE06-02359
| Final | 8/23/2006 | 8/24/2006 | 8/24/2006 9:50:45 AM | A | PASS |
|
|
darryl; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok to final
|
ELE06-02360
| Final | 8/23/2006 | 8/24/2006 | 8/24/2006 9:34:30 AM | A | PASS |
|
|
darryl; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok to final
|
ELE06-03153
| Temporary Service | 8/23/2006 | 8/24/2006 | 8/24/2006 8:57:08 AM | A | CANC |
|
|
Internet Inspection Request from: Latisha Peltier talked to contr, wrong address
|
ELE06-02633
| Electrical Rough-In | 8/23/2006 | 8/24/2006 | 8/24/2006 8:53:31 AM | A | PASS |
|
|
Partial rough-in steel stud walls only Contact Ric; Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok to cover walls only plus bath lid
|
ELE06-02906
| Electrical Rough-In | 8/23/2006 | 8/24/2006 | 8/24/2006 8:33:03 AM | A | FAIL |
|
|
craig; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt met owner, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.17(C) nm cable shall be secured within 8" of box, BCC all make-up shall be done-boxes set
|