BLD03-02347
| Extend Permit 180 days | 8/20/2007 | 8/20/2007 | | P | |
|
|
|
FIR07-00690
| INSP-Final Inspection | 8/24/2007 | 8/24/2007 | 8/27/2007 5:19:56 PM | P | FAIL |
|
|
HVAC is not wired to the duct detector to enable shutdown of the unit.
|
FIR07-00148
| FIR-Aging Inspection | 8/24/2007 | 8/24/2007 | 8/27/2007 10:59:14 AM | | DEFR |
|
|
Work in progress.
|
BLD06-02000
| FIRE-Final Inspection | 8/24/2007 | 8/24/2007 | 8/27/2007 9:33:34 AM | P | DEFR |
|
|
###-#### - derick
|
BLD07-00292
| FIRE-Conference | 8/23/2007 | 8/24/2007 | 8/24/2007 4:30:03 PM | P | NH |
|
|
Contractor not available on site or telephone at the time of field visit.
|
BLD07-01043
| FIRE-Final Inspection | 8/23/2007 | 8/24/2007 | 8/24/2007 4:18:48 PM | A | NR |
|
|
Project related fire sprinkler permit failed inspection.
|
FIR07-00474
| INSP-Final Inspection | 8/24/2007 | 8/24/2007 | 8/24/2007 4:18:02 PM | P | FAIL |
|
|
Overspaced heads at four locations.
|
FIR07-00448
| INSP-Sprinkler Rough-in | 8/23/2007 | 8/24/2007 | 8/24/2007 2:55:19 PM | P | FAIL |
|
|
Insulation at the roof deck is still obstructing upright head coverage, also missing cold cavity protection at the concealed spaces above the riser and lobby.
|
FIR06-00007
| INSP-Final Inspection | 8/23/2007 | 8/24/2007 | 8/24/2007 2:47:25 PM | A | PART |
|
|
1st floor fire alarm testing completed today, items remaining for the 1st floor include lacking HD at the elevator machine room and missing main FACP door.
|
FIR06-00759
| INSP-Final Inspection | 8/22/2007 | 8/24/2007 | 8/24/2007 12:55:14 PM | P | PART |
|
|
Pressure relief valve, test header and associated piping install completed satisfactory, final pending functional testing of the PRV.
|
BLD07-01120
| FIRE-Final Inspection | 8/23/2007 | 8/24/2007 | 8/24/2007 11:49:32 AM | A | PASS |
|
|
Noted corrections have been completed, TI modification fire life safety inspection passed.
|
FIR07-00166
| INSP-Alarm Testing | 8/23/2007 | 8/24/2007 | 8/24/2007 11:47:24 AM | A | PART |
|
|
Re-inspection for the fire alarm work associated with the 4th floor remodel BLD07-01120 passed, remainder of alarm permit scope of work not yet completed.
|
FIR07-00460
| INSP-Final Inspection | 8/23/2007 | 8/24/2007 | 8/24/2007 11:44:48 AM | A | PASS |
|
|
Required corrections have been verified for compliance, final alarm testing passed, permit finaled.
|
FIR07-00645
| INSP-Final Inspection | 8/24/2007 | 8/24/2007 | 8/24/2007 11:43:16 AM | A | PASS |
|
|
Fire sprinkler permit work passed final inspection.
|
BLD07-01374
| FIRE-Final Inspection | 8/23/2007 | 8/24/2007 | 8/24/2007 11:42:03 AM | A | FAIL |
|
|
Need to provide visual indicator at the main entry/exit door, EM lighting at the warehouse area failed to function.
|