Inspections for the day of: Friday, August 24, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-00913 FIRE-Final Inspection8/23/20078/24/20078/27/2007 2:29:48 PMPCANC
Need the project related fire alarm and fire sprinkler permits finaled prior to performing this inspection
FIR07-00727 INSP-Sprinkler Rough-in8/23/20078/24/20078/24/2007 4:00:58 PMPPASS
The pharmacy area piping is ok to cover
BLD07-01424 FIRE-Conference8/24/20078/24/20078/24/2007 3:58:37 PMPDONE
I let the electrician know that the manual pull station for the hood suppression system is to be mounted 10' to 20' from the hood in the path of egress.
FIR06-00011 INSP-Alarm Testing8/24/20078/24/20078/24/2007 3:16:31 PMPDONE
See Mike Timmermans notes for items tested today.
FIR07-00616 INSP-Sprinkler Rough-in8/24/20078/24/20078/24/2007 3:15:32 PMPFAIL
The sprinkler rough-in is ok but the second floor tenting is not adequate. The locations have been marked on the approved plans.
BLD07-01999 FIRE-Final Inspection8/24/20078/24/20078/24/2007 3:13:44 PMPFAIL
Provide approved door hardware and sprinkler protection for the new room. The sprinkler work will require a permit.
FIR07-00658 INSP-Final Inspection8/23/20078/24/20078/24/2007 1:14:45 PMPFAIL
The duct smoke detectors are mounted on the long side of the rectrangular duct not the short side. The duct smoke detectors will need to be tested after they have been relocated. The sample tubes will need to be changed.
FIR07-00544 INSP-Sprinkler Rough-in8/23/20078/24/20078/24/2007 12:47:28 PMAPASS
The sprinkler piping above the hardlids is ok to cover.
MIS07-00151 FIR-Final8/23/20078/24/20078/24/2007 12:16:53 PMAPASS
life safety passed.
BLD05-03028 FIRE-Final Inspection8/23/20078/24/20078/24/2007 11:17:24 AMAPASS
life safety passed
BLD07-01185 FIRE-Final Inspection8/23/20078/24/20078/24/2007 10:27:42 AMAPASS
Life safety passed.
FIR07-00479 INSP-Sprinkler Rough-in8/23/20078/24/20078/24/2007 10:26:33 AMAPASS
Three more sprinkler heads in the first floor corridor are ok to cover. Rick removed conduit that was attached to the piping as I waited.