BLD07-00913
| FIRE-Final Inspection | 8/23/2007 | 8/24/2007 | 8/27/2007 2:29:48 PM | P | CANC |
|
|
Need the project related fire alarm and fire sprinkler permits finaled prior to performing this inspection
|
FIR07-00727
| INSP-Sprinkler Rough-in | 8/23/2007 | 8/24/2007 | 8/24/2007 4:00:58 PM | P | PASS |
|
|
The pharmacy area piping is ok to cover
|
BLD07-01424
| FIRE-Conference | 8/24/2007 | 8/24/2007 | 8/24/2007 3:58:37 PM | P | DONE |
|
|
I let the electrician know that the manual pull station for the hood suppression system is to be mounted 10' to 20' from the hood in the path of egress.
|
FIR06-00011
| INSP-Alarm Testing | 8/24/2007 | 8/24/2007 | 8/24/2007 3:16:31 PM | P | DONE |
|
|
See Mike Timmermans notes for items tested today.
|
FIR07-00616
| INSP-Sprinkler Rough-in | 8/24/2007 | 8/24/2007 | 8/24/2007 3:15:32 PM | P | FAIL |
|
|
The sprinkler rough-in is ok but the second floor tenting is not adequate. The locations have been marked on the approved plans.
|
BLD07-01999
| FIRE-Final Inspection | 8/24/2007 | 8/24/2007 | 8/24/2007 3:13:44 PM | P | FAIL |
|
|
Provide approved door hardware and sprinkler protection for the new room. The sprinkler work will require a permit.
|
FIR07-00658
| INSP-Final Inspection | 8/23/2007 | 8/24/2007 | 8/24/2007 1:14:45 PM | P | FAIL |
|
|
The duct smoke detectors are mounted on the long side of the rectrangular duct not the short side. The duct smoke detectors will need to be tested after they have been relocated. The sample tubes will need to be changed.
|
FIR07-00544
| INSP-Sprinkler Rough-in | 8/23/2007 | 8/24/2007 | 8/24/2007 12:47:28 PM | A | PASS |
|
|
The sprinkler piping above the hardlids is ok to cover.
|
MIS07-00151
| FIR-Final | 8/23/2007 | 8/24/2007 | 8/24/2007 12:16:53 PM | A | PASS |
|
|
life safety passed.
|
BLD05-03028
| FIRE-Final Inspection | 8/23/2007 | 8/24/2007 | 8/24/2007 11:17:24 AM | A | PASS |
|
|
life safety passed
|
BLD07-01185
| FIRE-Final Inspection | 8/23/2007 | 8/24/2007 | 8/24/2007 10:27:42 AM | A | PASS |
|
|
Life safety passed.
|
FIR07-00479
| INSP-Sprinkler Rough-in | 8/23/2007 | 8/24/2007 | 8/24/2007 10:26:33 AM | A | PASS |
|
|
Three more sprinkler heads in the first floor corridor are ok to cover. Rick removed conduit that was attached to the piping as I waited.
|