Inspections for the day of: Monday, August 24, 2009.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01092 ELE-Aging Inspection8/24/20098/24/20098/28/2009 3:46:32 PM DONE
no activity, waiting for call for final, no esc this project
ESC09-00397 General Inspection8/24/20098/24/20098/24/2009 3:54:50 PMPPASS
looked ok
ESC09-00021 General Inspection8/24/20098/24/20098/24/2009 3:39:29 PMPPASS
looked ok
ELE09-01556 Electrical Rough-In8/21/20098/24/20098/24/2009 3:37:21 PMPPASS
Please call Jeff Creek at ###-#### if any corrections. Thanks, Andrea. Phone #: ###-#### Internet Inspection Request from: Andrea Creek met contractor, ric ok, no esc this project
ELE09-01457 Electrical Rough-In8/24/20098/24/20098/24/2009 2:56:19 PMPFAIL
Alan Phone #: ###-#### called, left correction notice, BCC all u/g shall be inspected before cover, fee due
ELE09-01369 Electrical Rough-In8/24/20098/24/20098/24/2009 1:44:16 PMPPASS
Ben Phone #: ###-#### ok to cover under floor for addition only, no esc this project
ELE09-01559 Temporary Service8/24/20098/24/20098/24/2009 12:33:17 PMPFAIL
Ron Phone #: ###-#### called, left correction notice, NEC 110.12(B) there shall be no parts that are damaged- cable is cut, 250.53(G) rod electrode upper end shall be flush with or below ground, 408.4 shall provide circuit directory, 590.6(B)(1) shall provide gfci protection for personnel or (2) assured grounding program, 400.5(A) shall provide minimum #4 cord cable and type hard usage and type "W" ratings for wet locations, BCC shall post job id sticker, fee due
ELE09-00828 Electrical Rough-In8/21/20098/24/20098/24/2009 11:35:14 AMAPASS
This inspection will be for an overhead ceiling inspection. Would like an early inspection if possible please. Contact is Rey. Thank you have a wonderful day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw met 412, with 370 looked at ceilings lumper area, ok to cover ceilings only, looked at pull boxes for cabling, told they need to re-pull #6 conductors with correct colors, no esc this project
ELE09-01142 Final8/21/20098/24/20098/24/2009 10:38:48 AMACANC
Dave ###-#### called contractor to reschedule, floors were done over week-end , could not do inspection because of fumes, no esc this project
ELE09-01500 Electrical Rough-In8/19/20098/24/20098/24/2009 10:22:29 AMAPASS
Ran new washer and dryer circuit from panel to new laundry location. Replacing existing circuits. Brian ###-#### Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ric ok, will call for final, no esc this project
ELE09-01523 Permanent Service8/21/20098/24/20098/24/2009 9:47:11 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Tim Lawrence corrections made, p/s o/h rec ok, no esc this project
ELE09-01433 Final8/21/20098/24/20098/21/2009 10:51:00 AMPCANC
Eric Phone #: ###-#### Inspection cancelled from web by: Erick Baker