ELE09-01092
| ELE-Aging Inspection | 8/24/2009 | 8/24/2009 | 8/28/2009 3:46:32 PM | | DONE |
|
|
no activity, waiting for call for final, no esc this project
|
ESC09-00397
| General Inspection | 8/24/2009 | 8/24/2009 | 8/24/2009 3:54:50 PM | P | PASS |
|
|
looked ok
|
ESC09-00021
| General Inspection | 8/24/2009 | 8/24/2009 | 8/24/2009 3:39:29 PM | P | PASS |
|
|
looked ok
|
ELE09-01556
| Electrical Rough-In | 8/21/2009 | 8/24/2009 | 8/24/2009 3:37:21 PM | P | PASS |
|
|
Please call Jeff Creek at ###-#### if any corrections. Thanks, Andrea. Phone #: ###-#### Internet Inspection Request from: Andrea Creek met contractor, ric ok, no esc this project
|
ELE09-01457
| Electrical Rough-In | 8/24/2009 | 8/24/2009 | 8/24/2009 2:56:19 PM | P | FAIL |
|
|
Alan Phone #: ###-#### called, left correction notice, BCC all u/g shall be inspected before cover, fee due
|
ELE09-01369
| Electrical Rough-In | 8/24/2009 | 8/24/2009 | 8/24/2009 1:44:16 PM | P | PASS |
|
|
Ben Phone #: ###-#### ok to cover under floor for addition only, no esc this project
|
ELE09-01559
| Temporary Service | 8/24/2009 | 8/24/2009 | 8/24/2009 12:33:17 PM | P | FAIL |
|
|
Ron Phone #: ###-#### called, left correction notice, NEC 110.12(B) there shall be no parts that are damaged- cable is cut, 250.53(G) rod electrode upper end shall be flush with or below ground, 408.4 shall provide circuit directory, 590.6(B)(1) shall provide gfci protection for personnel or (2) assured grounding program, 400.5(A) shall provide minimum #4 cord cable and type hard usage and type "W" ratings for wet locations, BCC shall post job id sticker, fee due
|
ELE09-00828
| Electrical Rough-In | 8/21/2009 | 8/24/2009 | 8/24/2009 11:35:14 AM | A | PASS |
|
|
This inspection will be for an overhead ceiling inspection. Would like an early inspection if possible please. Contact is Rey. Thank you have a wonderful day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw met 412, with 370 looked at ceilings lumper area, ok to cover ceilings only, looked at pull boxes for cabling, told they need to re-pull #6 conductors with correct colors, no esc this project
|
ELE09-01142
| Final | 8/21/2009 | 8/24/2009 | 8/24/2009 10:38:48 AM | A | CANC |
|
|
Dave ###-#### called contractor to reschedule, floors were done over week-end , could not do inspection because of fumes, no esc this project
|
ELE09-01500
| Electrical Rough-In | 8/19/2009 | 8/24/2009 | 8/24/2009 10:22:29 AM | A | PASS |
|
|
Ran new washer and dryer circuit from panel to new laundry location. Replacing existing circuits. Brian ###-#### Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ric ok, will call for final, no esc this project
|
ELE09-01523
| Permanent Service | 8/21/2009 | 8/24/2009 | 8/24/2009 9:47:11 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tim Lawrence corrections made, p/s o/h rec ok, no esc this project
|
ELE09-01433
| Final | 8/21/2009 | 8/24/2009 | 8/21/2009 10:51:00 AM | P | CANC |
|
|
Eric Phone #: ###-#### Inspection cancelled from web by: Erick Baker
|