FIR09-00033
| INSP-Sprinkler Rough-in | 8/21/2009 | 8/24/2009 | 8/24/2009 4:29:03 PM | P | PART |
|
|
Completed rough-in inspections for systems 23 and 24 including coverage at six rooftop towers, pallet storage single interlock systems 16,17, and 18, reinspection for correction items at system 25, discussed remaining issues at systems 14, 18 and 21 including pipe size changes, racks at the scan room, obstruction at HVAC piping, coverage at ceiling elevation change between system 14 and 11, and inspection schedule for project related FIR 09-00296 fire alarm permit for VESDA and preaction system releasing panel site acceptance testing set for the first requested inspection 8/25.
|
FIR09-00033
| INSP-Sprinkler Rough-in/Hydro | 8/24/2009 | 8/24/2009 | 8/24/2009 4:14:26 PM | A | PART |
|
|
Hydrostatic retest of rack system #6 at the dry goods warehouse passed.
|
BLD08-01105
| FIRE-Final Inspection | 8/21/2009 | 8/24/2009 | 8/24/2009 4:12:46 PM | A | PART |
|
|
Items on C/N verified for compliance, fire life safety is satisfactory pending completion of the loop road at the north end of the building and completion of finishes at the dental office.
|
BLD09-00467
| FIRE-Final Inspection | 8/21/2009 | 8/24/2009 | 8/24/2009 4:10:16 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
FIR09-00477
| INSP-Final Inspection | 8/21/2009 | 8/24/2009 | 8/24/2009 4:09:37 PM | A | FAIL |
|
|
Missing fire alarm notification at two restrooms.
|
FIR09-00033
| INSP-Alarm Testing | 8/21/2009 | 8/24/2009 | 8/24/2009 12:57:46 PM | P | NR |
|
|
Pending FIR09-00296
|
FIR09-00033
| INSP-Alarm Testing | 8/21/2009 | 8/24/2009 | 8/24/2009 12:57:12 PM | A | NR |
|
|
Pending FIR09-00296
|
FIR09-00347
| INSP-Final Inspection | 8/21/2009 | 8/24/2009 | 8/21/2009 9:40:44 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 8/21/2009 at 9:39:55 AM. Disp set to [CANC] by a contractor via Hello! on Aug 21 2009 9:40AM.
|