Inspections for the day of: Tuesday, August 24, 2010.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00582 FIR-Aging Inspection8/24/20108/24/20109/1/2010 4:54:49 PM DONE
FIR08-00764 FIR-Aging Inspection8/24/20108/24/20108/24/2010 4:38:25 PM FAIL
Need site inspection request for permit final.
FIR10-00408 INSP-Sprinkler Rough-in8/24/20108/24/20108/24/2010 4:28:43 PMPPART
Okayed overhead cover at new pendent heads in the sheetrock ceilings. See clouded locations marked with today's date on stamped plans.
FIR10-00054 INSP-Sprinkler Rough-in/Hydro8/24/20108/24/20108/24/2010 4:26:11 PMPPART
Hydrostatic test of the overhead wet system passed. Begin 24 hour pneumatic test of the new preaction system @ 11:45 AM 42psig.
BLD10-01335 FIRE-Final Inspection8/24/20108/24/20108/24/2010 4:23:32 PMPFAIL
Corrections include door hardware, exit signs, missing field ceiling tile, project related fire sprinkler permit needs finaled, etc. Discussed project finish schedule.
FIR08-00696 FIR-Aging Inspection8/24/20108/24/20108/24/2010 2:41:01 PM FAIL
Pending repair and retest of correction notice items.
BLD10-01906 FIRE-Final Inspection8/24/20108/24/20108/24/2010 2:37:39 PMAFAIL
Missing two exit signs, post signage at the main entry door, provide approved single action door hardware at the north exit. See plan red-lines and review conditions for details. Discussed occupancy and timeline for completion of noted correction items.
BLD10-01335 FIRE-Conference8/24/20108/24/20108/24/2010 2:34:02 PMADONE
Regarding fire extinguisher regulations.
BLD10-01249 FIRE-Final Inspection8/23/20108/24/20108/24/2010 2:32:34 PMAPASS
Fire life safety passed, corrections verified for completion.
FIR10-00341 INSP-Final Inspection8/24/20108/24/20108/24/2010 2:31:51 PMAPASS
Fire sprinkler permit finaled.