FIR08-00582
| FIR-Aging Inspection | 8/24/2010 | 8/24/2010 | 9/1/2010 4:54:49 PM | | DONE |
|
|
|
FIR08-00764
| FIR-Aging Inspection | 8/24/2010 | 8/24/2010 | 8/24/2010 4:38:25 PM | | FAIL |
|
|
Need site inspection request for permit final.
|
FIR10-00408
| INSP-Sprinkler Rough-in | 8/24/2010 | 8/24/2010 | 8/24/2010 4:28:43 PM | P | PART |
|
|
Okayed overhead cover at new pendent heads in the sheetrock ceilings. See clouded locations marked with today's date on stamped plans.
|
FIR10-00054
| INSP-Sprinkler Rough-in/Hydro | 8/24/2010 | 8/24/2010 | 8/24/2010 4:26:11 PM | P | PART |
|
|
Hydrostatic test of the overhead wet system passed. Begin 24 hour pneumatic test of the new preaction system @ 11:45 AM 42psig.
|
BLD10-01335
| FIRE-Final Inspection | 8/24/2010 | 8/24/2010 | 8/24/2010 4:23:32 PM | P | FAIL |
|
|
Corrections include door hardware, exit signs, missing field ceiling tile, project related fire sprinkler permit needs finaled, etc. Discussed project finish schedule.
|
FIR08-00696
| FIR-Aging Inspection | 8/24/2010 | 8/24/2010 | 8/24/2010 2:41:01 PM | | FAIL |
|
|
Pending repair and retest of correction notice items.
|
BLD10-01906
| FIRE-Final Inspection | 8/24/2010 | 8/24/2010 | 8/24/2010 2:37:39 PM | A | FAIL |
|
|
Missing two exit signs, post signage at the main entry door, provide approved single action door hardware at the north exit. See plan red-lines and review conditions for details. Discussed occupancy and timeline for completion of noted correction items.
|
BLD10-01335
| FIRE-Conference | 8/24/2010 | 8/24/2010 | 8/24/2010 2:34:02 PM | A | DONE |
|
|
Regarding fire extinguisher regulations.
|
BLD10-01249
| FIRE-Final Inspection | 8/23/2010 | 8/24/2010 | 8/24/2010 2:32:34 PM | A | PASS |
|
|
Fire life safety passed, corrections verified for completion.
|
FIR10-00341
| INSP-Final Inspection | 8/24/2010 | 8/24/2010 | 8/24/2010 2:31:51 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|