BLD11-00610
| FIRE-Conference | 8/17/2011 | 8/22/2011 | | A | |
|
|
Troy-call Dixie for am meeting
|
BLD11-00101
| FIRE-Final Inspection | 8/24/2011 | 8/24/2011 | 8/24/2011 3:12:25 PM | P | CANC |
|
|
Todays inspection only covered the exit signs and emergency lights. See the electrical sheets of the city approved plans for the locations of exit signs and emergency lights that failed to operate.
|
FIR11-00159
| INSP-Final Inspection | 8/24/2011 | 8/24/2011 | 8/24/2011 2:46:49 PM | P | FAIL |
|
|
The wet system tamper switches are not reporting to the central station. Need to perform the forward flush.
|
FIR11-00139
| INSP-Final Inspection | 8/24/2011 | 8/24/2011 | 8/24/2011 2:45:49 PM | P | FAIL |
|
|
Todays inspection was for the the manual pull stations,elevator recall and retesting the wet sprinkler system tamper switches. A manual pull station is required at the lower level east exit doors. The tamper switches did not report to the monitoring station. The outside alarm bell now functions.
|
BLD11-00380
| FIRE-Conference | 8/24/2011 | 8/24/2011 | 8/24/2011 2:42:32 PM | P | DONE |
|
|
JR and I discussed fire alarm remote annunciator requirements.
|
FIR11-00239
| INSP-Final Inspection | 8/23/2011 | 8/24/2011 | 8/24/2011 12:07:29 PM | A | PASS |
|
|
Permit finaled
|