Inspections for the day of: Friday, August 24, 2012.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-02003 FIRE-Final Inspection8/24/20128/24/20128/24/2012 3:55:10 PMPPASS
life safety passed. lights have been repaired.
FIR12-00373 INSP-Final Inspection8/21/20128/24/20128/24/2012 3:52:13 PMPCANC
Chris and I agreed to reschedule this test for monday afternoon since I am overbooked.
FIR11-00543 INSP-Sprinkler Rough-in8/23/20128/24/20128/24/2012 3:34:51 PMPPART
Earthquaking in the basement has been correct and piping can now be covered. The rough-in for the piping in the Chiller is basically ok except a upright has been installed in a pendant position, one upright needs to be change and installed as a pendant to clear a beam and the hydraulic calculations need to be resubmitted for the chiller room since seven 1" elbows have been installed on one of the branchlines to the heads in the remote area.
BLD11-01269 FIRE-Final Inspection8/24/20128/24/20128/24/2012 3:31:36 PMPPASS
Life safety passed
BLD11-01269 FIRE-Alarm Testing8/24/20128/24/20128/24/2012 2:50:36 PMPDONE
Alarm testing was previously completed.
FIR12-00351 INSP-Final Inspection8/23/20128/24/20128/24/2012 1:20:09 PMAFAIL
Phone lines 1 and 2, flow switch, tamper switches and hvac units 3 and 4 tested ok. Stopped inspection due to monitor modules being wired incorrectly and shipping plugs still installed in the duct detectors. Signals sent were verified through ADT. Need as-builts showing the additional tamper switches.
BLD12-02003 FIRE-Final Inspection8/22/20128/24/20128/24/2012 9:53:56 AMAFAIL
Repair the three existing exit signs
BLD10-02526 FIRE-Final Inspection8/23/20128/24/20128/24/2012 9:12:51 AMAPASS
life safety passed