Inspections for the day of: Monday, August 24, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00394 FIR-Aging Inspection8/24/20158/24/20158/31/2015 11:56:21 AM PEND
Project is currently being inspected
BLD15-02549 FIRE-Final Inspection8/24/20158/24/20158/24/2015 3:13:20 PMPPASS
life safety passed
BLD15-02511 FIRE-Final Inspection8/24/20158/24/20158/24/2015 2:59:34 PMPPART
*Per Scott Arellano* TCO is authorized with interior exit signage completion and structural field inspector verification of signage. Exterior exit discharge lighting shall be completed prior to final sign off.

Troy Cobbley - I actually performed two inspections here today. The first inspection I noted that I need verification that the fire alarm system has been activated, all ceiling tile installed and all exit signs/emergency lights/exit discharge lights installed and functional.
Upon my return visit in the afternoon I found tha the fire alarm system is now active but ceiling tile and lights have not been completed. Per electrician the lights will not be finished until tomorrow afternoon.
FIR15-00421 INSP-Final Inspection8/24/20158/24/20158/24/2015 2:20:13 PMAPASS
Permit finaled
FIR15-00503 INSP-Final Inspection8/24/20158/24/20158/24/2015 1:42:13 PMPPASS
Permit finaled
BLD15-02036 FIRE-Final Inspection8/21/20158/24/20158/24/2015 12:53:21 PMPPART
Life safety in Open Office 101 is complete. Contractor will need to resubmit plans showing the deleted scope of work and the revise exiting (exit sign locations), for approval, in Open Office 101. Also it appears door 101C needs panic hardware.
FIR15-00529 INSP-Final Inspection8/24/20158/24/20158/24/2015 12:48:39 PMPPART
Sprinkler work in Open Office 101 is complete.
BLD15-02936 FIRE-Final Inspection8/21/20158/24/20158/24/2015 9:31:10 AMAFAIL
Need revise floor plan showing the office walls. It appears that the return air grill is in the "not shown office" with the supply registers out side of this office.
FIR15-00583 INSP-Alarm Testing8/24/20158/24/20158/24/2015 12:00:00 AMPCANC
Peter Phone #: ###-####