FIR11-00394
| FIR-Aging Inspection | 8/24/2015 | 8/24/2015 | 8/31/2015 11:56:21 AM | | PEND |
|
|
Project is currently being inspected
|
BLD15-02549
| FIRE-Final Inspection | 8/24/2015 | 8/24/2015 | 8/24/2015 3:13:20 PM | P | PASS |
|
|
life safety passed
|
BLD15-02511
| FIRE-Final Inspection | 8/24/2015 | 8/24/2015 | 8/24/2015 2:59:34 PM | P | PART |
|
|
*Per Scott Arellano* TCO is authorized with interior exit signage completion and structural field inspector verification of signage. Exterior exit discharge lighting shall be completed prior to final sign off.
Troy Cobbley - I actually performed two inspections here today. The first inspection I noted that I need verification that the fire alarm system has been activated, all ceiling tile installed and all exit signs/emergency lights/exit discharge lights installed and functional. Upon my return visit in the afternoon I found tha the fire alarm system is now active but ceiling tile and lights have not been completed. Per electrician the lights will not be finished until tomorrow afternoon.
|
FIR15-00421
| INSP-Final Inspection | 8/24/2015 | 8/24/2015 | 8/24/2015 2:20:13 PM | A | PASS |
|
|
Permit finaled
|
FIR15-00503
| INSP-Final Inspection | 8/24/2015 | 8/24/2015 | 8/24/2015 1:42:13 PM | P | PASS |
|
|
Permit finaled
|
BLD15-02036
| FIRE-Final Inspection | 8/21/2015 | 8/24/2015 | 8/24/2015 12:53:21 PM | P | PART |
|
|
Life safety in Open Office 101 is complete. Contractor will need to resubmit plans showing the deleted scope of work and the revise exiting (exit sign locations), for approval, in Open Office 101. Also it appears door 101C needs panic hardware.
|
FIR15-00529
| INSP-Final Inspection | 8/24/2015 | 8/24/2015 | 8/24/2015 12:48:39 PM | P | PART |
|
|
Sprinkler work in Open Office 101 is complete.
|
BLD15-02936
| FIRE-Final Inspection | 8/21/2015 | 8/24/2015 | 8/24/2015 9:31:10 AM | A | FAIL |
|
|
Need revise floor plan showing the office walls. It appears that the return air grill is in the "not shown office" with the supply registers out side of this office.
|
FIR15-00583
| INSP-Alarm Testing | 8/24/2015 | 8/24/2015 | 8/24/2015 12:00:00 AM | P | CANC |
|
|
Peter Phone #: ###-####
|