BLD15-03489
| FIRE-Conference | 8/23/2017 | 8/24/2017 | 8/24/2017 1:31:12 PM | A | DONE |
|
|
Fire conference complete
|
BLD17-01715
| FIRE-Final Inspection | 8/24/2017 | 8/24/2017 | 8/24/2017 1:11:20 PM | P | FAIL |
|
|
Associated FIR permit for fire sprinkler work needs to be finaled (FIR17-00405 was in issued status at time of life fire safety inspection). Emergency egress light needs to be installed in breakroom per city approved drawings. Provide emergency egress lighting in west lobby to include exit discharge on the west lobby exterior door. Exit sign above west lobby exit needs to be serviced, exit light did not stay illuminated when test button was pressed. Fire extinguisher will be mounted in discussed location.
|
NAF17-00051
| INSP-Sprinkler Rough-in | 8/23/2017 | 8/24/2017 | 8/24/2017 12:12:31 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting complete, approved for cover.
|
FIR17-00217
| INSP-Sprinkler Rough-in/Hydro | 8/24/2017 | 8/24/2017 | 8/24/2017 11:38:11 AM | P | FAIL |
|
|
Insulation needs to be removed where pipe is covered, overhead fire sprinkler piping could not be inspected in numerous area's due to cover from insulation. Hangers are overspaced in numerous area's on level 1, FDC piping going from riser to standpipe has no hangers/straps installed. Overhead fire sprinkler piping on level 1 cannot be covered until rough to cover inspection is complete and passed.
|
FIR17-00217
| INSP-Sprinkler Rough-in/Hydro | 8/23/2017 | 8/24/2017 | 8/24/2017 11:34:12 AM | A | PASS |
|
|
Hydrostatic test for level 1 complete
|
FIR17-00001
| INSP-Final Inspection | 8/23/2017 | 8/24/2017 | 8/24/2017 11:13:04 AM | P | CANC |
|
|
Inspection request cancelled per conversation with Anthony Phone #: ###-####, inspection will be rescheduled for a later date.
|
FIR17-00067
| INSP-Sprinkler Rough-in | 8/23/2017 | 8/24/2017 | 8/24/2017 10:39:55 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping on systems 10-3, 20-7 and 20-11 complete, approved for cover. Notated the city approved drawings with green highlighter/red ink systems that were inspected.
|
BLD17-01500
| FIRE-Final Inspection | 8/24/2017 | 8/24/2017 | 8/24/2017 8:55:17 AM | A | PASS |
|
|
No fire sprinklers, fire alarm inspection complete, fire extinguisjers are in place with current inspection tags (fire extinguisher inspection tags expire at the end of August) Final life fire safety inspection passed/complete.
|
FIR17-00419
| INSP-Final Inspection | 8/23/2017 | 8/24/2017 | 8/24/2017 8:53:54 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD17-00654
| FIRE-Final Inspection | 8/24/2017 | 8/24/2017 | 8/24/2017 8:13:29 AM | A | PASS |
|
|
Previously noted fire alarm issues have been repaired and final inspection complete. Final life fire safety inspection passed/complete.
|
FIR17-00351
| INSP-Final Inspection | 8/24/2017 | 8/24/2017 | 8/24/2017 8:12:26 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR17-00351
| INSP-Alarm Testing | 8/18/2017 | 8/24/2017 | 8/24/2017 8:10:31 AM | A | DONE |
|
|
Fire alarm testing complete
|