ELE18-02675
| Electrical Rough-In | 8/24/2018 | 8/24/2018 | 8/24/2018 2:13:25 PM | P | PASS |
|
|
Ceiling cover for parameter classrooms Phone #: ###-#### Inspection requested via web by Ron Zimmerman Perimeter class rooms only grid rough in ok cover.
|
ELE18-03125
| Electrical Rough-In | 8/23/2018 | 8/24/2018 | 8/24/2018 12:32:02 PM | A | PASS |
|
|
Pls contact Brad (Foreman) @ ###-#### or Preston (Electrician) @ ###-#### on hour prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes Listing confirmed, rough in ok
|
ELE18-03193
| Electrical Rough-In | 8/23/2018 | 8/24/2018 | 8/24/2018 12:31:23 PM | A | FAIL |
|
|
Addition at rear of House, enter thru iron side gate. Any questions..... call. Phone #: ###-#### Inspection requested via web by Douglas Hackney
680.27(C)- Heaters shall not be located with in 5' horizontal of inside edge of tub. 680.43(A)- All 120 volt 15 and 20 amp receptacle outlets shall be more than 6' from inside edge of hot tub. 680.43(B)- Lighting outlets located above or with in 5' horizontal of inside edge with GFCI protection shall not be with in 7'6" of waters edge. exception- recessed or surface mounted non-metallic or metallic with metallic isolated from contact permited below 7'6" if plastic or glass lense globe, GFCI protected, and damp location rated. 680.43(C)- Switches shall not be located with in 5' measured horizontal from inside edge of hot tub. Discussed exhaust fan located below deck shall not need horizontal clearance due to barrier however bonding and GFCI protection required.
|
ELE18-02555
| Final | 8/23/2018 | 8/24/2018 | 8/24/2018 9:56:04 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Final ok
|
ELE18-03140
| Rough-In Permanent Service | 8/23/2018 | 8/24/2018 | 8/24/2018 9:36:31 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|