Inspections for the day of: Friday, August 24, 2018.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03335 Final8/23/20188/24/20188/24/2018 4:03:29 PMPNH
This guy is only available from 3 - 3:30. Don Davidson ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- called Don and tried to leave a message and rang the door bell and no one answered.
MEC18-04147 Final8/24/20188/24/20188/24/2018 3:43:13 PMPPASS
LATE P.M. FINAL PLEASE
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- furnace co ok
MEC18-04004 Final8/20/20188/24/20188/24/2018 3:14:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace ac coil co ok
MEC18-04144 DOC - Permit Finaled8/24/20188/24/20188/24/2018 2:56:35 PMPPASS
MEC18-04144 Rough-in8/23/20188/24/20188/24/2018 2:55:51 PMPPASS
Phone #: ###-#### Inspection requested via web by Nicholas Paige- R/I cover ok
MEC18-03990 Final8/23/20188/24/20188/24/2018 2:25:49 PMPFAIL
please call when you are on your way so we can let you in the house. Phone #: ###-#### Inspection requested via web by Dan McFate
- need drip leg in gas line furnace- line set insulation needs fixed about furnace
MEC18-02864 Final8/24/20188/24/20188/24/2018 2:00:57 PMPNR
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- not ready
MEC18-04122 Final8/22/20188/24/20188/24/2018 1:46:07 PMPFAIL
Please inspect in the PM and call on way: Maddie ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss
-5lb flue pressure test was under 5lb
MEC18-03812 Rough-in8/23/20188/24/20188/24/2018 1:21:11 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves
- line set insulation has rips in the attic and the line set doesnt penetrate the exterior wall
- duct seal at furnace
- exhaust fans need duct seal with tape( downstairs)
- need nail plate upstairs on exhaust in wall
- need to see a 5lb flue test
-20lb gas pressure gauge would not zero
- water heater flue on the roof needs support
MEC18-03812 Pressure Test8/23/20188/24/20188/24/2018 1:18:29 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gauge wont zero
- need to see a 5lb flue test
MEC18-04072 Final8/22/20188/24/20188/24/2018 11:22:57 AMAFAIL
Final. Gas fireplace insert. Arlin Gomm is homeowner/point of contact Phone #: ###-#### Inspection requested via web by Sheldon Lebow
- need a sleeve on gas line through fireplace side wall- eletrical installed for fireplace is in violation of code- need to hire a certified electrical contractor to installed per code requirements
MEC17-04167 Mec-Aging Inspection8/24/20188/24/20188/24/2018 11:18:03 AM DONE
called pipe ko and left a message about mec aging permit
MEC18-02078 Final8/24/20188/24/20188/24/2018 11:14:28 AMAPASS
IT room in airport final ok
MEC18-02078 Rough-in8/22/20188/24/20188/24/2018 11:13:35 AMAPASS
rough in - call mark Phone #: ###-#### Inspection requested via web by Brandon Sorensen- R/I ok
MEC18-04064 Final8/22/20188/24/20188/24/2018 10:24:12 AMAPASS
Please call prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace ac coil co ok
MEC18-02864 Rough-in8/23/20188/24/20188/24/2018 10:08:05 AMAPASS
flue re-inspect Phone #: ###-#### Inspection requested via web by Brandon Sorensen
- unit number 7 5 lb flue test ok
-still need to see condensates done by others
- need to see hard lid access doors by others
- line sets on roof need supports and line set penentrations need sealed on roof
- all this for a final
MEC18-03723 Final8/23/20188/24/20188/24/2018 9:35:18 AMAPASS
early as possible please Phone #: ###-#### Inspection requested via web by fritz ramisch
MEC18-03520 Final8/24/20188/24/20188/24/2018 9:13:04 AMPFAIL
furnace ac coil
-need to add A/C to permit
- need to see 5lb flue pressure test
-need to check furnace clearances to closet door based on manufacturers specs
-need to also check combustion air for furnace whether its coming from the crawl and attic or if you need to install a two pipe system
-